Download Print this page

Honeywell Ademco VISTA-128BPT Integration Note page 5

Hide thumbs Also See for Ademco VISTA-128BPT:

Advertisement

P
P
ANEL
ROGRAMMING
Before communication can start between the g! system and the Ademco panel there are several fields
that need to be changed in the panel configuration. You will need the installer access code to enter the
programming mode.
To enter programming mode press the installer code and then [8000]. Once in programming mode,
changing the value of a field can be accomplished by pressing [*] + [Field #] + [ Value ]. The keypad will
ding 3 times and advance to the next field after the value had been entered. For example: Programming
field 70 to a value of 11111 requires the following key strokes [*] + [70] + [1] + [1] + [1] + [1] + [1]. To exit
the programming mode, press [*] + [99]. If you cannot gain entry to the programming menu using the
installer code then this method of access may be locked out on the device. The only way to access the
unit in that case is by pressing [*] and [#] simultaneously within 30 seconds of the device powering up.
The panel will need to be disconnected from power and the backup battery to create this condition.
Step
Instructions
1
Press [Installer Code] + [8000]
2
Press [*] + [05] + [1]
3
Press [*] + [14] + [1]
5
Press [*] + [94]
6
Press [*] + [70] + [1]+[1]+[1]+[1] +[1]
7
Press [*] + [72] + [0]
8
Press [*] + [78] + [1]
9
Press [*] + [79] + [1]+[1]+[1]+[1] +[1]
10
Press [*] + [80] +[1]
13
Press [*] + [99]
14
Press [*] + [99]
Press [*] + [99]
Comments
Enter programming mode on page (0)
Sets field *05 to 1 and enables System Events Notify
Sets field *14 to 1 and enables RS-232 Input
Changes to the next page(1)
Sets field 1*70 to 11111 and enables Event log types
Alarm, Check, Bypass, Open/Close and System
Sets field 1*72 to 0 and disables the Event Log
Printer On- Line Printer
Sets field 1*78 to 1 and enables a Extended Home
Control Event Reports
Sets field 1*79 to 11111 and enables Event log types
Alarm, Check, Bypass, Open/Close and System
Sets field 1*80 to 1 and enables Log Faults and
Restores. See Note below
To change to previous page (1)
To change to previous page (0)
To exit programming mode
5 of 7

Advertisement

loading

This manual is also suitable for:

Ademco vista-250bpt