The safety instructions must be followed at all times during the start-up procedure, see
Safety.
Note! Check that starting the motor does not cause any danger.
1. Apply mains power
The first time the drive is powered up, it is controlled from
the Control Terminals (remote control, REM).
To switch to control panel use (local control, LOC), press
and hold the MENU and ENTER buttons down
simultaneously until first Loc is displayed.
2. Check Parameters
The following parameters must be set
using the information from the motor
name plate (see example on right).
9905
MOTOR NOM VOLT
9906
MOTOR NOM CURR
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
9909
MOTOR NOM POWER
9910
MOTOR COS PHI
ACS 160 User's Manual
REM
OUTPUT
LOC
OUTPUT
ABB Motors
Motor 3~
Cl. F IP55 IEC34
M2AA 080A
3GAA 082 001-ASA
V
Hz
r/min
380-420 Y
50
1420
220-240 D
50
1420
440-480 Y
60
1700
0.0
Hz
FWD
MENU
LOC REM
ENTER
0.0
Hz
FWD
Cos ϕ ϕ ϕ ϕ
kW
A
0.55
1.5
0.74
0.55
2.6
0.74
0.65
1.5
0.73
23