Download Print this page

Honeywell Ex-Or Digital Gold Series Installation And Commissioning Instructions page 8

Digital detector with regulating photocell

Advertisement

Dimensions
MLS2421DF/DALIF
62mm deep
behind ceiling
100mm
Technical Data
MLS CABLE : 1.5mm unscreened twisted-pair (applicable when detector is used as part of a
full MLS Digital Managed Lighting System): see Application Note AN4001
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION: 10 Amps
MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 10 Amps
MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Approx 7m dia at 2.4m ceiling height
OFF DELAY: 1 min - 96 hours plus 10-second walk-test mode
PHOTOCELL: Passive/Active/Regulating adjustable 50-5000 lux
MATERIAL: Flame retardant PC/ABS
COLOUR: White RAL 9010
WEIGHT: 243g (flush version), 251g (surface version)
IP RATING: 2X
OPERATING TEMPERATURE: 0 C to 40 C
Honeywell Ex-Or
St. Marks Court, North Street,
Horsham, West Sussex, RH12 1BW, UK
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com