It is the operator that allows to set tone and volume for zone groups via the CBE of inverse groups.
TONE (Zone Volume Range Tone)
Where :
Tone = sound type in range 1 ÷ 33
Volume = volume in range 1 ÷ 4
Range_di_Zone = list of zones to activate the pattern (tone and volume) in Zxxx format: Zyyy
(example Z1: Z10 to indicate zones from zone 1 to zone 10)
It is the operator that allows you to retrieve the silence of the control panel
Example: An output module equation is: (TAC (SYS))
When the siren silence command is executed in the control panel, the output module will be activated
is the operator which allows to program some activation delays for specific conditions.
The device which has in its CBE equation the "DEL" operator, when its equation is true, waits for the
programmed time before activating.
If during this delay time its equation is not true any longer, the timer resets and is ready to start at the next event
(therefore the output device does not activate)
FORMAT : OF (MM.SS (delay) MM.SS. (duration - optional) (CONDITION) equation which sets the delay
start))
Where:
MM = minutes (2 digits), SS = seconds (2 digits)
CONDITION = it can be an equation of the type:
Element = it can be GXXX for a group (1  400) - LXX S/MXX for an addressable point
Example 1: if the equation of the G90 software group is DEL(00.30 01.30(G21)) then:
- After 30 Sec. from the G21 activation
- the G90 group will activate and will be active for 1 minute and 30 seconds
Example 2: if the equation of the L2M90 output module is DEL (00.30 00.30 (AND (L1S1 L1S4)))
- After the L1S2 and L1S4 sensors have been in alarm condition for 30 seconds, the L2M90 module will be
active for 30 seconds.
N. B.
If a delay is entered = 00.00, then the equation will be active AS SOON AS the delay start equation
is active, and it is active for the time period specified in "duration".
Only a DEL operator can exist for each equation
AM_8200
AM82000_manu-prog-ENG
TAC(SYS)
XGRP (GXXX)
NOT (Element 1...)
OR (Element 1...Element 2...)
AND (Element 1...Element 2..)
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
DEL
Insert a
space character
PAGE - 67
NOTIFIER ITALIA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents