IDR-2P, -2A & -6A Repeaters User Manual

Appendix 1 - Specification

Mechanical
Construction:
Dimensions (mm):
Weight:
Fixing:
Cable Entry:
Terminals:
Environmental:
Climatic classification:
Operating temperature: -5°C to +45°C, (recommended +5°C
Humidity:
Height above sea level: Maximum, 2000m
Panel sealing:
Vibration:
EMC:
Safety:
Electrical
Operating Voltage:
Quiescent Current:
Alarm Current:
Maximum Fault Current: Resettable thermal fuse. Nominal -
Comms. Medium:
Address Range:
RS485 Isolated Serial Port
Isolation:
Baud rate:
Connector:
Maximum cable length: 3000m (minimum of 1mm
A1 - 1
Mild steel sheet enclosure. All displays
and controls are carried on the
enclosure door.
165.0(h) x 253.5(w) x 50.0(d)
1.7kg approx.
Three mounting holes in enclosure
4 x 20mm knockouts in top of enclosure
3 x 20mm knockouts in back of enclosure
External connections made using
screw terminals capable of accepting
cable sizes between 0.5mm
2
2.5mm
3K5, (IEC 721-2-3)
to 35°C)
5% to 95% R.H.
IP 30, (EN 60529)
EN 60068-2-6, 10-150Hz at 0.981ms
(Meets the requirements of EN 54-2/4)
Emissions:
EN 50081-1
Immunity:
EN 50130-4
EN 60950
18-32V
90mA
120mA (-2A/-2P), 155mA (-6A)
250mA; absolute max. 600mA
RS485 2-wire serial link or RS232 link
Switch-selectable in range 0-63
(maximum address depends upon the
type of fire panel, and the type of
network used. Master/Slave: address
0 is unmonitored and must not be used
except during power-up commissioning
2
check. ID
net: address 0 cannot be
used)
Functional at 42V
1200 Baud
Screw terminals on Termination Board
cable recommended)
997-411-000-9, Issue 9
2
and
-2
2
screened
March 2008