ACH580 Installation, Operation and Maintenance Manual
Default control connections for the HVAC default
0...10 V DC speed
reference signal
Start/Stop signal
Not
es:
1)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the grounding shelf for
the control cables.
2)
Connected with jumpers at the factory.
3)
Only frames R6...R11 have terminals 40 and 41 for external 24 V AC/DC input.
Terminal sizes:
1. R1...R5: 24...14 AWG (0.2...2.5 mm
2. 26...16 AWG (0.14...1.5 mm
3. R6...R9: 26...14 AWG (0.14...2.5 mm
4. Tightening torques: 0.4 lb-ft (0.5...0.6 Nm
Input Signals
Analog frequency/speed reference (AI1)
Start/stop selection (DI1)
Constant speed/frequency selection (DI3)
Start interlock 1 (DI4)
X1
1
+
2
-
3
4
5
6
7
8
9
X2 & X3
10
11
12
13
14
15
Safety
16
17
18
X6, X7, X8 Relay outputs
19
20
21
22
23
24
Run status
25
26
Fault status
27
X5
29
30
31
S4
S5
X4
34
35
36
37
38
2
): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2
): Terminals DI, AI, AO, AGND, RO, STO
2
) (all terminals)
HVAC default direct I/O control
Reference voltage and analog inputs and outputs
SCR
Signal cable shield (screen)
AI1
Output frequency/speed reference: 0 to 10 V
AGND
Analog input circuit common
+10 V
+10V
Reference voltage 10 V DC
AI2
Actual feedback: 0 to 20 mA
AGND
Analog input circuit common
Output frequency: 0 to 10 V
AO1
AO2
Motor current: 0 to 20 mA
AGND
Analog output circuit common
Aux. voltage output and programmable digital inputs
+24 V
+24V
Aux. voltage output +24 V DC, max. 250 mA
DGND
Aux. voltage output common
DCOM
Digital input common for all
DI1
Stop (0)/Start (1)
DI2
Not configured
DI3
Constant frequency/speed selection
DI4
Start interlock 1 (1 = allow start)
DI5
Not configured
DI6
Not configured
RO1C
Damper control
RO1A
250 V AC / 30 V DC
2 A
RO1B
RO2C
Running
RO2A
250 V AC / 30 V DC
2 A
RO2B
RO3C
Fault (-1)
RO3A
250 V AC / 30 V DC
RO3B
2 A
Embedded fieldbus
B+
A-
Embedded fieldbus, EFB (EIA-485)
DGND
TERM
Termination switch
Bias resistors switch
BIAS
Safe torque off
OUT1
OUT2
Safe torque off
SGND
IN1
IN2
Output signals
Analog output AO1: Output frequency
Analog output AO2: Motor current
Relay output 1: Damper control
Relay output 2: Running
Relay output 3: Fault (-1)
41
Energize damper
19 connected to 21
Running
22 connected to 24
Fault condition
25 connected to 26
ACH580-01 Installation