6. Close the warning pop-up, enter site name, and click Save.
7. Wait for the dashboard to load. Click the center of the Time Sync widget and perform a
time synchronization between the Pulse Accumulator and the PC by clicking Sync.
8. Navigate to View/Edit > Configure by Group > Site Information and change the Site ID to
the value required by Meter Data Management software.
9. Navigate to View/Edit > Configure by Group > Modem Call-in Configuration, and set the
following parameters for call-in.
Item No.
Description
333
Call-in Trigger
449
Switch Filtering
486
Modem AT-Command Enable
334
Scheduled Call-In Date
335
Scheduled Call-In Time
336
Call-In Retry By
339
Scheduled Call-In Phone number
485
Call-Out Stop Time
490
Call-Out Start Time
493
Alarm Call-In Phone number
495
Modem Retry Interval A
496
Modem Retry Interval B
497
Modem Retry A Count
10. Click Disconnect to disconnect MasterLink from the Pulse Accumulator. The following
message is displayed upon a successful disconnection from the Pulse Accumulator.
Close the pop-up.
CNI4 Quick Start Guide
Recommended Value
3 = Alarm & Scheduled Call-in
1 = Filter Both Channels
1-yes
Set the desired call-in date
Set the desired call-in time
Instrument
<IP>/<Port>,
Example:192.168.1.1/50467
00:00:00
00:00:00
<IP>/<Port>
Example: 192.168.1.1/50467
5 minutes
1440 minutes
3
6