Honeywell 7800 Series Installation Instructions Manual page 8

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7895A,B,C,D/EC7895A,C; RM7896A,C,D7800 SERIES Relay Modules
Terminal
Number
G
Flame Sensor Ground
Earth G
Earth Ground
L2(N)
Line Voltage Common
3
Alarm
4
Burner Motor
5
Line Voltage Supply (L1)
6
Burner Controller and Limits
7
Lockout Interlock
8
Pilot Valve/Ignition
9
Main Fuel Valve
10
Ignition
F(11)
Flame Sensor
12 to 20
Unused
21
2nd Stage Main Valve
(EC7895C, RM7895C,D;
RM7896C,D)
22
Shutter
a
See Table 2.
b
2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly.
c
See Tables 4 and 5.
d
220-240 Vac to 120 Vac, 10 VA minimum stepdown transformer (not provided) must be used to drive the shutter. The transformer is NOT
needed for UV flame sensor models C7061A1020, C7061A1079 and C7061F1003 (combined with R7861-series flame amplifiers), which
have an internal selectable terminal block to connect 230V shutter output from EC7895 models directly.
Combination Number
1
2
3
4
5
6
7
8
9
a
RM7895C,D: EC7895C, RM7896C,D only, jumper terminals 8 to 9.
A
4.5A ignition
a
Pilot Duty refers to solenoid-type valves.
32-00156-03
Table 3. Terminal Ratings.
Description
a
120 Vac, 1A pilot duty.
120 Vac, 9.8A AFL, 58.8 ALR
(inrush).
120 Vac (+10/-15%), 50 or 60 Hz
(±10%).
120 Vac, 1 mA.
120 Vac, 8A run, 43A inrush.
120 Vac
120 Vac
120 Vac
60 to 220 Vac, current limited.
120 Vac
120 Vac, 0.5A
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Pilot Fuel 8
C
B
Fa
F
Fa
D
Da
D
Da
Table 5. Composition of each Combination.
B
a
50 VA Pilot Duty
plus
4.5A ignition.
RM7895/RM7896
b
c
c
c
c
Main 9
F
No Load
F
No Load
No Load
A
F
A
No Load
A
F
A
No Load
A
D
A
No Load
A
C
180 VA Ignition plus
2A Pilot Duty.
motor valves with:
660 VA inrush,
360 VA open,
240 VA hold.
8
Ratings
EC7895
220-240 Vac, 1A pilot duty.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac (+10/-15%), 50 or 60 Hz
(±10%).
220-240 Vac, 1 mA.
8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 2A at PF = 0.2
60 to 220 Vac, current limited.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
d
220-240 Vac
Ignition 10
Delayed Main Valve 21
No Load
No Load
No Load
No Load
F
No Load
D
No Load
D
D
a
65 VA Pilot Duty
motor valves with:
3850 VA inrush,
700 VA open,
250 VA hold.
F
a
plus