GE AF-650 GP Programming Manual page 117

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
3
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option:
[0]
Hold set-up
[1] *
Resume set-up
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.
Option:
[0] *
Do not reset
[1]
Do reset
O-07 Diagnosis Trigger
Option:
116
Runs the motor at maximum frequency until communication resumes.
Stops the motor, then resets the frequency converter in order to restart: via the network, via the reset
button on the Keypad or via a digital input.
Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function
defines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the
time-out function.
See [7] Select setup 1
See [7] Select setup 1
See [7] Select setup 1
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].
Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout toggles. Then the frequency converter resumes its original set-up.
Resumes the set-up active prior to the time-out.
Function:
Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.
Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting
Function:
This parameter enables and controls the frequency converter diagnosis function and permits expansion
of the diagnosis data to 24 byte.
NB!
This is only valid for Profibus.
-
Disable [0]: Do not send extended diagnosis data even if they appear in the frequency converter.
-
Trigger on alarms [1]: Send extended diagnosis data when one or more alarms appear in alarm
par. DR-90 Alarm Word or par. PB-53 Profibus Warning Word.
-
Trigger alarms/warn. [2]: Send extended diagnosis data if one or more alarms or warnings
appear in alarm par. DR-90 Alarm Word, par. PB-53 Profibus Warning Word, or warning par.
DR-92 Warning Word.
AF-650 GP Programming Guide