GE AF-650 GP Programming Manual

GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

GE
AF-650 GP
TM
General Purpose Drive
Programming Guide

Advertisement

Table of Contents
loading

Summary of Contents for GE AF-650 GP

  • Page 1 AF-650 GP General Purpose Drive Programming Guide...
  • Page 2: Table Of Contents

    Contents AF-650 GP Programming Guide Contents 1 Introduction 1.1 Software Version 1.2 Approvals 1.3 Symbols 1.4 Definitions 1.4.1 Frequency Converter 1.4.2 Input 1.4.3 Motor 1.4.4 References 1.4.5 Miscellaneous 1.5 Safety 1.6 Electrical Wiring 1.6.1 Electrical Wiring - Control Cables 1.7 External Hand Off Auto Example 2 How to Program 2.1 The Keypad...
  • Page 3 Contents AF-650 GP Programming Guide 3.6 P-## Motor Data 3.7 H-## High Perf Parameters 3.8 AN-## Analog In/Out 3.9 SP-## Special Functions 3.10 O-## Options/Comms 3.11 DN-## DeviceNet Fieldbus 3.12 PB-## Profibus 3.13 EN-## Ethernet 3.14 EC-## Feedback Option 3.15 RS-## Resolver Interface 3.17 ID-## Drive Information...
  • Page 4 Contents AF-650 GP Programming Guide 5 Troubleshooting 5.1 Status Messages 5.1.1 Warnings/Alarm Messages Index DET-618C...
  • Page 5: Introduction

    Programming Guide Software version: 2.31 DRIVE,MAX Maximum output current. This Programming Guide can be used for all AF-650 GP frequency converters with software version 2.31. DRIVE,N The software version number can be seen from ID-43 Software Rated output current supplied by the frequency converter.
  • Page 6: References

    Introduction AF-650 GP Programming Guide Preset Reference A defined preset reference to be set from -100% to +100% Synchronous motor speed of the reference range. Selection of eight preset references 2 × − 04 × 60 − 01 via the digital terminals.
  • Page 7 Introduction AF-650 GP Programming Guide Keypad Drive Standard Bus The keypad makes up a complete interface for control and Includes RS-485 bus with drive protocol or MC protocol. programming of the frequency converter. The keypad is See O-30 Protocol. detachable and can be installed up to 3 m from the Thermistor frequency converter, i.e.
  • Page 8: Safety

    Introduction AF-650 GP Programming Guide functions are not sufficient. In such cases the mains supply must be disconnected. 1.5 Safety The motor may start while setting the WARNING parameters. If this means that personal safety may be compromised (e.g. personal injury caused...
  • Page 9 Introduction AF-650 GP Programming Guide NOTE WARNING Crane, Lifts and Hoists: High Voltage The controlling of external brakes must always have a Touching the electrical parts may be fatal - even after the redundant system. The frequency converter can in no equipment has been disconnected from mains.
  • Page 10: Electrical Wiring

    Introduction AF-650 GP Programming Guide 1.6 Electrical Wiring 1.6.1 Electrical Wiring - Control Cables Illustration 1.2 Basic Wiring Schematic Drawing. A=Analog, D=Digital Terminal 37 is used for Safe Stop. For Safe Stop installation instructions, refer to the Design and Installation Guide DET-767.
  • Page 11 Introduction AF-650 GP Programming Guide 1.6.2 Start/Stop Input polarity of control terminals Terminal 18 = E-01 Terminal 18 Digital Input [8] Start Terminal 37 = Safe stop (where available) Illustration 1.3 PNP (Source) Illustration 1.6 Start/Stop Illustration 1.4 NPN (Sink) NOTE Control cables must be screened/armoured.
  • Page 12 Introduction AF-650 GP Programming Guide 1.6.3 Pulse Start/Stop 1.6.5 Potentiometer Reference Terminal 18 = E-01 Terminal 18 Digital Input Latched start, Voltage reference via a potentiometer Reference Source 1 = [1] Analog input 53 (default) Terminal 27= E-03 Terminal 27 Digital Input Stop inverse, [6]...
  • Page 13: External Hand Off Auto Example

    Set K-11 Edit Set-up to [9] Active Set-up. This is recommended because then the active setup will Illustration 1.10 GE 30 mm HOA Cat# (1) 104PSG34B & (3) always be the set-up that is edited. If you prefer CR104PXC1...
  • Page 14: How To Program

    How to Program AF-650 GP Programming Guide 2 How to Program 2.1 The Keypad The easiest programming of the frequency converter is performed by the keypad. The keypad is divided into four functional groups Graphical display with Status lines. Menu keys and indicator lights - changing parameters and switching between display functions.
  • Page 15: The Lcd-Display

    How to Program AF-650 GP Programming Guide 2.1.1 The LCD-Display The LCD-display has backlight and a total of 6 alpha- numeric lines. The display lines show the direction of rotation (arrow), the chosen set-up as well as the programming set-up. The display is divided into 3 sections.
  • Page 16 How to Program AF-650 GP Programming Guide press [OK]. Information is displayed about the condition of [Hand] the frequency converter before it enters the alarm mode. enables control of the frequency converter via the keypad. [Hand ] also starts the motor, and it is now possible to [Back] enter the motor speed data by means of the arrow keys.
  • Page 17: Quick Transfer Of Parameter Settings Between Multiple Frequency Converters

    How to Program AF-650 GP Programming Guide 2.1.2 Quick Transfer of Parameter Settings Data transfer from keypad to frequency converter NOTE between Multiple Frequency Converters Stop the motor before performing this operation. Go to K-50 Keypad Copy Once the set-up of a frequency converter is complete,...
  • Page 18: Parameter Set-Up

    How to Program AF-650 GP Programming Guide Operating variable Unit DR-20 Motor Angle DR-30 DC Link Voltage DR-32 Brake Energy /s DR-33 Brake Energy /2 min DR-34 Heatsink Temp. DR-35 Drive Thermal DR-36 Drive Nominal Current DR-37 Drive Max. Current DR-38 Logic Controller State Illustration 2.10 Status screen I...
  • Page 19: Quick Menu Key Functions

    How to Program AF-650 GP Programming Guide 2.1.6 Quick Menu Key Functions Select Parameter Data Check to get information about: ▲ ▼ • the last 10 changes. Use the [ ] navigation Pres [Quick Menus] to see a list of different areas keys to scroll between the last 10 changed contained in the Quick menu.
  • Page 20 How to Program AF-650 GP Programming Guide 2.1.7 Initial Commissioning The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up procedure (read Table 2.3 from left to right). The example applies to open loop applications.
  • Page 21: Main Menu Mode

    How to Program AF-650 GP Programming Guide 2.1.8 Main Menu Mode 2.1.10 Changing Data Start the Main Menu mode by pressing [Main Menu]. The The procedure for changing data is the same in the Quick read-out shown below appears on the display.
  • Page 22: Infinitely Variable Change Of Numeric Data Value

    How to Program AF-650 GP Programming Guide 2.1.13 Infinitely Variable Change of Numeric Data Value If the chosen parameter represents a numeric data value, ◀ ▶ select a digit with [ Illustration 2.20 Keypad Keys [Hand] enables control of the frequency converter via the keypad.
  • Page 23: Restoring Drive To Factory Settings

    How to Program AF-650 GP Programming Guide 2.1.17 Restoring Drive to Factory Settings The drive can be restored to factory settings in two ways. Recommended Select H-03 Restore Factory Settings Press [OK] Select [2] Restore Factory Settings Press [OK] Cut off the mains supply and wait until the display turns off.
  • Page 24: Parameter Descriptions

    Parameter Descriptions AF-650 GP Programming Guide 3 Parameter Descriptions 3.1 Parameter Selection Parameters for AF-650 GP are grouped into various parameter groups for easy selection of the correct parameters for optimized operation of the frequency converter. Main Menu Item Parameter groups:...
  • Page 25: K-## Keypad Set-Up

    Parameter Descriptions AF-650 GP Programming Guide 3.2 K-## Keypad Set-Up K-04 Operating State at Power-up Option: Function: Parameter group related to the fundamental functions of Selects the operating mode upon the drive, keypad buttons, configuration of the keypad reconnection of the frequency converter to display, copy-cat features, and password protection.
  • Page 26 Parameter Descriptions AF-650 GP Programming Guide K-10 Active Set-up Option: Function: Factory setup Cannot be changed. It contains the GE data set, and can be used as a data source when returning the other set-ups to a known state. Set-up 1...
  • Page 27 Parameter Descriptions AF-650 GP Programming Guide K-12 This Set-up Linked to K-13 Readout: Linked Set-ups Option: Function: Array [5] Range: Function: Index Keypad value {1,2} {1,2} Illustration 3.2 Set-up 1 Table 3.4 Example: Set-up 1 and Set-up 2 are linked K-14 Readout: Edit Set-ups / Channel 2.
  • Page 28 Parameter Descriptions AF-650 GP Programming Guide [1200] Control Word Present control word [1238] Logic Controller State of the event executed by the State control. [1201] Reference [Unit] Total reference (sum of digital/ analog/preset/bus/freeze ref./catch [1239] Control Card Temp. Temperature of the control card.
  • Page 29 Parameter Descriptions AF-650 GP Programming Guide [1284] Comm. Option STW Extended network communication K-25 Quick Start option status word. Array [50] [1285] Drive Port CTW 1 Control word (CTW) received from Define up to 50 parameters to appear in the Quick Start Menu, the Bus Master.
  • Page 30 Parameter Descriptions AF-650 GP Programming Guide The relation will depend on the type of unit selected in K-30 Unit for Custom Readout K-30 Unit for Custom Readout: Option: Function: [121] gal/s Unit Type Speed Relation [122] gal/min Dimensionless [123] gal/h...
  • Page 31 Parameter Descriptions AF-650 GP Programming Guide K-38 Display Text 2 K-41 [Off] Button on Keypad Range: Function: Option: Function: [0 - 0] Enter a text which can be viewed in the graphical Password without OFF display by selecting [38] Display Text 2 in Enabled, ref = 0 K-20 Display Line 1.1 Small, K-21 Display Line 1.2...
  • Page 32 Parameter Descriptions AF-650 GP Programming Guide K-50 Keypad Copy K-61 Access to Main Menu w/o Password Option: Function: Option: Function: No copy Keypad: No access Prevent unauthorized viewing and editing of Main Menu parameters. All to Keypad Copies all parameters in all set-ups from the...
  • Page 33: F-## Parameter Data Set

    Parameter Descriptions AF-650 GP Programming Guide 3.3 F-## Parameter Data Set F-03 Max Output Frequency 1 Range: Function: Parameter group related to the fundamental functions of NOTE the drive. Max. output frequency cannot exceed 10% of the carrier frequency (F-26 Motor 3.3.1 F-0# Fundamental 0...
  • Page 34 Parameter Descriptions AF-650 GP Programming Guide F-08 Decel Time 1 F-10 Electronic Overload Range: Function: Option: Function: corresponds to 0.01 s in speed mode. See accel input (H-96 KTY Thermistor Input). time in F-07 Accel Time 1. See 3.3.3.2 KTY Sensor Connection.
  • Page 35 Threshold level). Parameter set-up: AF-650 GP can handle three types of KTY sensors, defined Set F-10 Electronic Overload to [2] Thermistor Trip in H-95 KTY Sensor Type. The actual sensor temperature can Set F-12 Motor Thermistor Input to [6] Digital Input be read out from DR-19 KTY sensor temperature.
  • Page 36 Parameter Descriptions AF-650 GP Programming Guide 3.3.3.4 Klixon ® The Klixon type thermal circuit breaker uses a KLIXON metal dish. At a predetermined overload, the heat caused by the current through the disc causes a trip. Using a digital input and 24 V as power supply:...
  • Page 37 Parameter Descriptions AF-650 GP Programming Guide F-12 Motor Thermistor Input F-17 Motor Speed High Limit [RPM] Option: Function: Range: Function: NOTE 3600 [par. F-18 - Enter the maximum limit for motor 60000 RPM] speed. The Motor Speed High Limit can...
  • Page 38 Parameter Descriptions AF-650 GP Programming Guide F-23 Start Speed [Hz] F-25 Start Function Range: Function: Option: Function: 0 Hz [0 - This parameter can be used for hoist corresponds to the setting of the start current in F-29 Start Current.
  • Page 39 Parameter Descriptions AF-650 GP Programming Guide F-26 Motor Noise (Carrier Freq) F-38 Overmodulation Option: Function: Select the carrier frequency. Changing the switching frequency can help to reduce acoustic noise from the motor. Default motor shaft. This feature may be useful for depends on power size.
  • Page 40 Parameter Descriptions AF-650 GP Programming Guide F-43 Current Limit F-51 Reference/Feedback Unit Range: Function: Option: Function: 160.0 [1.0 - This is a true current limit function that [32] kg/h 1000.0 %] continues in the oversynchronous range, [33] t/min however due to field weakening the...
  • Page 41 Parameter Descriptions AF-650 GP Programming Guide F-52 Minimum Reference F-62 Catch up/slow Down Value Range: Function: Range: Function: closed loop, RPM; extended functionality with the DigiPot function. for [2] Torque, Nm. See parameter group F-9# Digital Pot-Meter. • The unit selected...
  • Page 42 Parameter Descriptions AF-650 GP Programming Guide F-68 Relative Scaling Reference Resource F-92 Power Restore Option: Function: Option: Function: Off Resets the Digital Pot-Meter reference to 0% after power up. On Restores the most recent Digital Pot-Meter reference at power up.
  • Page 43: E-## Digital In/Out

    Parameter Descriptions AF-650 GP Programming Guide 3.4 E-## Digital In/Out Parameter group related to the Digital Inputs/Outputs, additional accel/decel ramps, pulse inputs/outputs, and encoder input. 3.4.1 E-0# Digital Inputs Parameters to configure the Digital Inputs/Outputs and Safe Stop functions. Parameters for configuring the input functions for the input terminals.
  • Page 44 [80] Table 3.6 AF-650 GP standard terminals are 18, 19, 27, 29, 32 and 33. OPCGPIO General Purpose I/O Option Module terminals are X30/2, X30/3 and X30/4. Functions dedicated to only one digital input are stated in the associated parameter.
  • Page 45 Parameter Descriptions AF-650 GP Programming Guide Sends an inverted stop signal when the Preset ref. bit precise stop function is activated in Preset ref. 0 H-83 Precise Stop Function. Preset ref. 1 Precise stop inverse function is available for Preset ref. 2 terminals 18 or 19.
  • Page 46 Parameter Descriptions AF-650 GP Programming Guide [36] Mains failure Activates SP-10 Line failure. Mains failure E-02 Terminal 19 Digital Input inverse inverse is active in the Logic .0. situation. Option: Function: [41] Latched Precise Sends a latched stop signal when the...
  • Page 47 Parameter Descriptions AF-650 GP Programming Guide E-10 Accel Time 2 E-15 Decel Time 4 Range: Function: Range: Function: the output current does not exceed the current 3.00 [0.01 Enter the decel time from the rated motor speed limit in F-43 Current Limit during ramping. The - 3600 to 0 RPM.
  • Page 48 Parameter Descriptions AF-650 GP Programming Guide [11] At torque limit The torque limit set in F-40 Torque Limiter is a fault on the brake modules. Use the (Driving) or F-41 has been exceeded. output/relay to cut out the main voltage from the frequency converter.
  • Page 49 Parameter Descriptions AF-650 GP Programming Guide [72] Logic Rule 2 See parameter group LC-4#. If Logic Rule [122] No alarm Output is high when no alarm is present. 2 is evaluated as TRUE, the output will [123] Start command Output is high when there is an active go high.
  • Page 50 Parameter Descriptions AF-650 GP Programming Guide E-56 Term X30/6 Digi Out (OPCGPIO) E-27 Off Delay, Relay Array[2]: Relay1[0], Relay2[1] This parameter is active when OPCGPIO General Purpose I/O Option Module is mounted in the frequency converter. Functions Range: Function: are described under E-2# Digital Outputs.
  • Page 51 Parameter Descriptions AF-650 GP Programming Guide E-63 Term. 29 High Ref./Feedb. Value E-69 Pulse Filter Time Constant #33 Range: Function: Range: Function: Select terminal 29 as a and dampens oscillations on the feedback digital input signal from the control. (E-52 Terminal 29 Mode = This is an advantage, e.g.
  • Page 52 Parameter Descriptions AF-650 GP Programming Guide 3.4.7 E-9# Bus Controlled E-73 Terminal 29 Pulse Output Variable Option: Function: Parameters to configure digital, relay and pulse train [119] Torque % lim outputs to be controlled by the serial communications. E-76 Terminal X30/6 Pulse Output Variable E-90 Digital &...
  • Page 53 Parameter Descriptions AF-650 GP Programming Guide E-96 Pulse Out #29 Timeout Preset Range: Function: configured as [48] Bus Ctrl Timeout in E-73 Terminal 29 Pulse Output Variable. And a time-out is detected. E-97 Pulse Out #X30/6 Bus Control Range: Function:...
  • Page 54: C-## Frequency Control Functions

    Parameter Descriptions AF-650 GP Programming Guide 3.5 C-## Frequency Control Functions C-05 Multi-step Frequency 1 - 8 Array [8] Parameter group related to the Jump Frequencies, Multi- Range: 0-7 step Frequencies, Job set-up, and Frequency Settings 2 Range: Function: and 3.
  • Page 55 Parameter Descriptions AF-650 GP Programming Guide C-21 Jog Speed [RPM] C-24 Quick Stop Ramp Type Range: Function: Select the ramp type, depending on requirements for acceleration and deceleration. A linear ramp will give constant [0 - par. Enter a value for the jog speed n acceleration during ramping.
  • Page 56 Parameter Descriptions AF-650 GP Programming Guide C-34 Frequency Command 3 Option: Function: up to three different reference signals. The sum of these reference signals defines the actual reference. No function Analog Input 53 Analog Input 54 Frequency input 29 Frequency input 33...
  • Page 57: P-## Motor Data

    Parameter Descriptions AF-650 GP Programming Guide 3.6 P-## Motor Data P-04 Auto Tune Option: Function: Parameter group related to setting motor data in the drive. (P-30 Stator Resistance (Rs) to P-35 Main Reactance (Xh)) at motor standstill. 3.6.1 P-0# Motor Data...
  • Page 58 Parameter Descriptions AF-650 GP Programming Guide NOTE P-05 Motor Cont. Rated Torque P-10 Slip Compensation Time Constant will not have effect Range: Function: when P-20 Motor Construction = [1] PM, non salient SPM. 0.1 Nm [0.1 - Enter the value from the motor nameplate 10000 Nm] data.
  • Page 59 Parameter Descriptions AF-650 GP Programming Guide P-27 Voltage filter time const. P-30 Stator Resistance (Rs) Range: Function: Range: Function: distort the calculated voltage and affect 1.4000 [0.0140 - Set the line to common stator resistance the stability of the system.
  • Page 60 Parameter Descriptions AF-650 GP Programming Guide P-33 Stator Leakage Reactance (X1) P-36 Iron Loss Resistance (Rfe) Range: Function: Range: Function: Use the X default setting. The 10000.000 [0 - Enter the equivalent iron loss frequency converter establishes 10000.000 resistance (R...
  • Page 61: H-## High Perf Parameters

    Parameter Descriptions AF-650 GP Programming Guide 3.7 H-## High Perf Parameters H-04 Auto-Reset (Times) Option: Function: Parameter group related to high performance functions in Manual reset Select [0] Manual reset, to perform a the drive. reset via [RESET] or via the digital inputs.
  • Page 62 Parameter Descriptions AF-650 GP Programming Guide NOTE H-09 Start Mode If [1] S-ramp Const Jerk is selected and the reference during Option: Function: ramping is changed the ramp time may be prolonged in This function makes it possible to catch a...
  • Page 63 Parameter Descriptions AF-650 GP Programming Guide of H-22 Motor Feedback Loss Timeout. Warning/Alarm 61 H-24 Tracking Error Function Feedback Error is related to the Motor Feedback Loss Option: Function: Function. Warning H-21 Motor Feedback Speed Error Trip Trip after Range:...
  • Page 64 Parameter Descriptions AF-650 GP Programming Guide H-40 Configuration Mode H-41 Motor Control Principle Option: Function: Option: Function: Select the application control principle to be special motor mode, for parallel connected used when a Remote Reference (i.e. via motors in special motor applications. When analog input or Network) is active.
  • Page 65 Parameter Descriptions AF-650 GP Programming Guide H-43 Torque Characteristics H-45 Local Mode Configuration Option: Function: Option: Function: NOTE Select which application configuration mode (H-40 Configuration Mode), i.e. This parameter cannot be adjusted while application control principle, to use when a the motor is running.
  • Page 66 With this parameter it is possible to make an adjustment of the shifting point NOTE where AF-650 GP changes between Flux model 1 and Flux model 2, which is useful in some H-50 Motor Magnetisation at Zero Speed will not have effect sensitive speed and torque control applications.
  • Page 67 Parameter Descriptions AF-650 GP Programming Guide H-53 Model Shift Frequency H-56 U/f Characteristic - F Range: Function: Range: Function: This parameter is an array parameter [0-5] and is only accessible when H-41 Motor Control Principle is set to [0] U/f.
  • Page 68 Parameter Descriptions AF-650 GP Programming Guide H-61 High Speed Load Compensation H-66 Min. Current at Low Speed Range: Function: Range: Function: 100 % [0 - 300 Enter the % value to compensate voltage in highest value adjusts H-66 Min. Current at Low Speed.
  • Page 69 Parameter Descriptions AF-650 GP Programming Guide H-72 Warning Speed Low H-77 Warning Feedback High Range: Function: Range: Function: 0 RPM [0 - par. Enter the n value. When the motor 999999.999 [par. H-76 - Enter the upper H-73 RPM] speed exceeds this limit, the display reads ReferenceFeed- 999999.999...
  • Page 70 Parameter Descriptions AF-650 GP Programming Guide H-80 Function at Stop H-83 Precise Stop Function Option: Function: Option: Function: solutions are available to pre-magnetize the open loop control. Achieves high repetitive machine for the first start command: precision at the stopping point.
  • Page 71 H-83 Precise Stop Function KTY sensors can be used for motor protecting (H-97 KTY Threshold level). H-87 Load Type AF-650 GP can handle three types of KTY sensors, defined Option: Function: in H-95 KTY Sensor Type. The actual sensor temperature can Passive load For conveyers, fan and pump applications.
  • Page 72 Parameter Descriptions AF-650 GP Programming Guide NOTE If the temperature of the motor is utilized through a thermistor or KTY sensor the PELV is not complied with in case of short circuits between motor windings and sensor. In order to comply with PELV the sensor must be extra isolated.
  • Page 73: An-## Analog In/Out

    Parameter Descriptions AF-650 GP Programming Guide 3.8.2 AN-1# Analog Input 53 3.8 AN-## Analog In/Out Parameter group related to the Analog Inputs and Parameters to configure the scaling and limits for Analog Outputs. Input 1 (terminal 53) AN-10 Terminal 53 Low Voltage 3.8.1 AN-0# Analog I/O Mode...
  • Page 74 Parameter Descriptions AF-650 GP Programming Guide AN-15 Terminal 53 High Ref./Feedb. Value AN-24 Terminal 54 Low Ref./Feedb. Value Range: Function: Range: Function: AN-13 Terminal 53 High 0 ReferenceFeed- [-999999.999 - Enter the analog Current. backUnit 999999.999 input scaling value ReferenceFeed-...
  • Page 75 Parameter Descriptions AF-650 GP Programming Guide AN-34 Term. X30/11 Low Ref./Feedb. Value AN-45 Term. X30/12 High Ref./Feedb. Value Range: Function: Range: Function: [-999999.999 - Sets the analog input scaling value to [-999999.999 - Sets the analog input scaling value 999999.999] correspond to the low voltage value 999999.999]...
  • Page 76 Parameter Descriptions AF-650 GP Programming Guide AN-50 Terminal 42 Output AN-50 Terminal 42 Output Option: Function: Option: Function: Current, then the setting of AN-52 Terminal 42 [140] Bus ctrl. An output value set from Network process Output Max Scale must be: 4-20 mA data.
  • Page 77 Parameter Descriptions AF-650 GP Programming Guide desired maximum current x 100 % AN-60 Terminal X30/8 Output . 10 100 = 200 % Option: Function: X30/8 [mA]. See options under parameter AN-50 Terminal 42 Output. AN-61 Terminal X30/8 Min. Scale Range:...
  • Page 78: Sp-## Special Functions

    Parameter Descriptions AF-650 GP Programming Guide 3.9 SP-## Special Functions Parameter group related to special functions with regards to Line Voltage, Reset Functions, Current Limit, Energy Savings, Derating, and Accel/Decel Ramp Types. SP-00 Fault Level Option: Function: Use this parameter to customize Fault levels. Use [0] Off with caution as it will ignore all Warnings &...
  • Page 79 Parameter Descriptions AF-650 GP Programming Guide 3.9.1 SP-1# Line On/Off SP-10 Line failure Option: Function: Parameters to configure actions taken for Line Failures, coast function at mains interruption, together with Input Fault, and Imbalance. a flying start which occurs when the mains is restored.
  • Page 80 Parameter Descriptions AF-650 GP Programming Guide SP-10 Line failure SP-10 Line failure Option: Function: Option: Function: reduce U to SP-11 Line Voltage at Input Fault*1.35 by increasing the speed. This will not succeed as the mains cannot be lowered. If running motoric. The same mechanism...
  • Page 81 Parameter Descriptions AF-650 GP Programming Guide SP-10 Line failure SP-14 Kin. Backup Time Out Option: Function: Range: Function: 60 s [0 - 60 This parameter defines the Kinetic Backup Time Out in flux mode when running on low voltage grids. If the supply voltage does not increase...
  • Page 82 Parameter Descriptions AF-650 GP Programming Guide 3.9.4 SP-4# Energy Savings SP-26 Trip Delay at Drive Fault Range: Function: Parameters to configure the energy optimization level in If value = 0, protection mode is disabled both the Variable Torque and Energy Savings modes.
  • Page 83 Parameter Descriptions AF-650 GP Programming Guide 3.9.5 SP-5# Environment SP-52 Fan Operation Select minimum speed of the main fan. Parameters to enable/disable the optional factory installed Option: Function: A1/B1 RFI Filter, and Fan Monitor and to configure an Auto Select [0] Auto to run fan only when internal output filter if installed.
  • Page 84 Parameter Descriptions AF-650 GP Programming Guide If S-ramps are selected then set the level of non-linear jerk SP-55 Output Filter compensation required. Set jerk compensation by defining Option: Function: the proportion of ramp-up and ramp-down times where Sine- This parameter sets a minimum allowed limit to acceleration and deceleration are variable (i.e.
  • Page 85 Parameter Descriptions AF-650 GP Programming Guide SP-76 Accel/Decel Time 2 Type SP-84 Accel/Decel Ramp 3 Type Option: Function: Option: Function: S-ramp Const S-ramp based on the values set in E-10 Accel constant acceleration during ramping. An S- ramp will give non-linear acceleration,...
  • Page 86 Parameter Descriptions AF-650 GP Programming Guide SP-92 Accel/Decel Ramp 4 Type SP-98 Decel Time 4 S-ramp Ratio at Decel. End Option: Function: Range: Function: Select the ramp type, depending on 50 % [1 - 99 %] Enter the proportion of the total decel time...
  • Page 87: O-## Options/Comms

    Parameter Descriptions AF-650 GP Programming Guide 3.10 O-## Options/Comms O-03 Control Word Timeout Time Range: Function: Parameter group related to communications and options. [0.1 - Enter the maximum time expected to pass 18000 s] between the reception of two consecutive 3.10.1 O-0# General Settings...
  • Page 88: Diagnosis Trigger

    Parameter Descriptions AF-650 GP Programming Guide O-05 End-of-Timeout Function O-07 Diagnosis Trigger Option: Function: Option: Function: Word Timeout Function is set to [7] Set-up 1, 0 - 5 Standard DP Standard DP Diagnose [8] Set-up 2, [9]Set-up 3 or [10] Set-up 4.
  • Page 89 Protocol. display. Drive MC Select the protocol for the drive (standard) For guidelines in selection of GE Drive profile and [1] PROFIdrive port. profile refer to the design guide of the related product. Modbus RTU For additional guidelines in the selection of [1] PROFIdrive profile...
  • Page 90 Terminal 42 Output Bus Control [663] Terminal X30/8 Bus Control Parameters to configure the standard telegram or custom [748] PCD Feed Forward telegram for the GE drive port. [890] Bus Jog 1 Speed [891] Bus Jog 2 Speed O-40 Telegram Selection...
  • Page 91 Parameter Descriptions AF-650 GP Programming Guide O-41 Parameters for Signals O-42 PCD Write Configuration Option: Function: Range: Function: [1235] Drive Thermal [41] Torque Limiter (Braking) [1238] Logic Controller State [52] Minimum Reference [1239] Control Card Temp. [53] Maximum Reference [1248] Speed Ref. After Ramp [RPM]...
  • Page 92 Parameter Descriptions AF-650 GP Programming Guide O-43 PCD Read Configuration O-50 Coasting Select Range: Function: Option: Function: [1250] External Reference Logic OR Activates Coast command via the network/ serial communication port OR via one of the [1251] Pulse Reference digital inputs.
  • Page 93 Parameter Descriptions AF-650 GP Programming Guide 3.10.6 O-8# Drive Port Diagnostics O-54 Reversing Select Option: Function: O-80 Bus Message Count Digital Select control of the frequency converter Range: Function: input reverse function via the terminals (digital input) and/or via the fieldbus.
  • Page 94: Dn-## Devicenet Fieldbus

    [2] INSTANCE 20/70 and [3] INSTANCE DN-01 Baud Rate Select 21/71 are available. Instances 100/150 and 101/151 are GE- Select the network transmission speed. The selection must specific. Instances 20/70 and 21/71 are correspond to the transmission speed of the master and the ODVA-specific AC Drive profiles.
  • Page 95 Parameter Descriptions AF-650 GP Programming Guide DN-11 Process Data Config Write DN-12 Process Data Config Read Select the process write data for I/O Assembly Instances 101/151. Select the process read data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] Elements [2] and [3] of this array can be selected.
  • Page 96 Parameter Descriptions AF-650 GP Programming Guide 3.11.3 DN-2# COS Filters DN-13 Warning Parameter Range: Function: Parameters to configure the filtering of Change of State [0 - View a DeviceNet-specific Warning word. One bit data. 65535] is assigned to every warning. Please refer to the...
  • Page 97 Parameter Descriptions AF-650 GP Programming Guide DN-31 Store Data Values Option: Function: Parameter values changed via DeviceNet are not automatically stored in non-volatile memory. Use this parameter to activate a function that stores parameter values in the EEPROM non-volatile memory, so changed parameter values will be retained at power- down.
  • Page 98: Pb-## Profibus

    Parameter Descriptions AF-650 GP Programming Guide 3.12 PB-## Profibus PB-15 PCD Write Configuration Array [10] Parameter group related to Field Installed Profibus DP Option: Function: Network Communications Option Module. [653] Terminal 42 Output Bus PB-00 Setpoint Control Range: Function: [663]...
  • Page 99 Parameter Descriptions AF-650 GP Programming Guide PB-16 PCD Read Configuration PB-22 Telegram Selection [10] Array Displays the Profibus message configuration. Option: Function: Option: Function: [1248] Speed Ref. After Ramp [RPM] [101] PPO 1 [1250] External Reference [102] PPO 2 [1251] Pulse Reference...
  • Page 100 Parameter Descriptions AF-650 GP Programming Guide PB-44 Fault Message Counter PB-63 Actual Baud Rate Range: Function: Option: Function: capacity is eight error events. The buffer and This parameter displays the actual counter are set to 0 upon reset or power-up.
  • Page 101 Parameter Descriptions AF-650 GP Programming Guide PB-71 Profibus Save Data Values PB-82 Defined Parameters (3) Option: Function: Array [116] No keypad access Parameter values changed via Profibus are not Read only automatically stored in non-volatile memory. Use this parameter to activate a function that...
  • Page 102 Parameter Descriptions AF-650 GP Programming Guide PB-94 Changed Parameters (5) Array [116] No keypad Address Read only Range: Function: [0 - 9999] This parameter displays a list of all the frequency converter parameters deviating from default setting. DET-618C...
  • Page 103: En-## Ethernet

    Parameter Descriptions AF-650 GP Programming Guide 3.13 EN-## Ethernet EN-07 Domain Name Range: Function: The parameters in this group are common for Ethernet IP [0 - 2147483647] Domain name of the attached network. and Modbus TCP. Can be automatically assigned when using DHCP network.
  • Page 104 Parameter Descriptions AF-650 GP Programming Guide EN-30 Warning parameter EN-14 Link Duplex Option: Function: Range: Function: Forces the duplex for each port to Full or Half [0000– Read only. Displays the Ethernet/IP specific 16-bit FFFF hex] Status-word. duplex. If EN-12 Auto Negotiation is set to: [ON], this parameter is read only.
  • Page 105 Parameter Descriptions AF-650 GP Programming Guide EN-37 COS Inhibit Timer EN-89 Transent Socket Channel Port Range: Function: Range: Function: [0–65.535 Read only Change-Of-State inhibit timer. If the [0–9999] Configures the TCP port-number for the transent option is configured for COS operation, this socket channel.
  • Page 106 Parameter Descriptions AF-650 GP Programming Guide EN-94 Broadcast Storm Protection Range: Function: -1 % [-1 - The built-in switch is capable of protecting the 20 %] switch system from receiving too many broadcast packages, which can use up network resources. The value indicates a percentage of the total bandwidth that is allowed for broadcast messages.
  • Page 107: Ec-## Feedback Option

    Parameter Descriptions AF-650 GP Programming Guide 3.14 EC-## Feedback Option EC-25 Clock Rate Range: Function: 3.14.1 EC-1# Inc. Enc. Interface 260 kHz [100 - 260 Set the SSI clock rate. With long kHz] encoder cables the clock rate must EC-10 Signal Type be reduced.
  • Page 108 Parameter Descriptions AF-650 GP Programming Guide EC-61 Feedback Signal Monitoring Select which reaction the frequency converter should take in case a faulty encoder signal is detected. The encoder function in EC-61 Feedback Signal Monitoring is an electrical check of the hardware circuit in the encoder system.
  • Page 109: Rs-## Resolver Interface

    Parameter Descriptions AF-650 GP Programming Guide 3.15 RS-## Resolver Interface 3.17 ID-## Drive Information RS-50 Poles Range: Function: Parameter group related to drive information such as operating data, hardware configuration and software [2 - 8] Set the number of poles on the resolver.
  • Page 110 Parameter Descriptions AF-650 GP Programming Guide NOTE ID-10 Trending Source The reset is carried out by pressing [OK]. Array [4] Option: Function: ID-07 Reset Running Hours Counter [1225] Torque [Nm] High Option: Function: [1230] DC Link Voltage [1232] Brake Energy /s...
  • Page 111: Alarm

    Parameter Descriptions AF-650 GP Programming Guide 3.17.3 ID-2# Historic Log ID-12 Trigger Event Select the trigger event. When the trigger event occurs, a View up to 50 data items logged up to the last reported window is applied to freeze the log. The log will then retain a trip.
  • Page 112 Function: [0 - 0] View the 8-digit number. 3.17.4 ID-3# Alarm Log ID-47 GE Power Card Model No View up to 10 alarm logs. The data is stored in array Range: Function: parameters, where [0] is the most recent and [9] is the [0 - 0] View the power card model number.
  • Page 113 Parameter Descriptions AF-650 GP Programming Guide ID-62 Option Ordering No Array [8] Range: Function: [0 - 0] Shows the ordering number for the installed options. ID-63 Option Serial No Array [8] Range: Function: [0 - 0] View the installed option serial number.
  • Page 114: Power [Kw]

    Parameter Descriptions AF-650 GP Programming Guide 3.18.2 DR-1# Motor Status 3.18 DR-## Data Read-outs Parameter group related to data readouts in the drive for Parameters to view the motor status values. references, voltages, control, alarms, warnings, and status DR-10 Power [kW] words.
  • Page 115: Torque [Nm]

    Parameter Descriptions AF-650 GP Programming Guide DR-16 Torque [Nm] DR-25 Torque [Nm] High Range: Function: Range: Function: 0 Nm [-3000 - View the torque value with sign, applied to show higher values than the standard readout in DR-16 Torque [Nm].
  • Page 116 Parameter Descriptions AF-650 GP Programming Guide DR-38 Logic Controller State DR-52 Feedback[Unit] Range: Function: Range: Function: [0 - 100] View the state of the event under execution by 0 ReferenceFeed- [-999999.999 - View the feedback unit the LC controller. backUnit 999999.999...
  • Page 117 Parameter Descriptions AF-650 GP Programming Guide 3.18.5 DR-6# Inputs/Outputs DR-63 Terminal 54 Switch Setting Option: Function: Parameters to view the digital and analog I/O status View the setting of input terminal 54. values. Current DR-60 Digital Input Voltage Range: Function: Pt 1000 [°C]...
  • Page 118 Parameter Descriptions AF-650 GP Programming Guide DR-72 Counter A DR-82 Fieldbus REF 1 Range: Function: Range: Function: [-2147483648 - View the present value of Counter A. [-200 - 200] View the two-byte word sent with the control 2147483647] Counters are useful as comparator word form the Bus-Master to set the reference operands, see LC-10 Comparator Operand.
  • Page 119 Parameter Descriptions AF-650 GP Programming Guide DR-94 Ext. Status Word Range: Function: [0 - 4294967295] Returns the extended warning word sent via the serial communication port in hex code. DET-618C...
  • Page 120: Lc-## Logic Controller

    Parameter Descriptions AF-650 GP Programming Guide 3.19 LC-## Logic Controller LC-01 Start Event Select the boolean (TRUE or FALSE) input to activate Logic Parameter group related to programming the drive's built- Controller. in Logic Controller. The Logic Controller consists of a series...
  • Page 121 Parameter Descriptions AF-650 GP Programming Guide LC-01 Start Event LC-02 Stop Event Select the boolean (TRUE or FALSE) input to activate Logic Select the boolean (TRUE or FALSE) input to deactivate Logic Controller. Controller. Option: Function: Option: Function: [44] Reset key [Reset] is pressed.
  • Page 122 Parameter Descriptions AF-650 GP Programming Guide LC-02 Stop Event LC-10 Comparator Operand Select the boolean (TRUE or FALSE) input to deactivate Logic Array [6] Controller. Option: Function: Option: Function: TRUE or FALSE, respectively. See [74] Logic Controller Time-out 7 Logic Controller timer 7 is LC-11 Comparator Operator.
  • Page 123 Parameter Descriptions AF-650 GP Programming Guide LC-10 Comparator Operand LC-10 Comparator Operand Array [6] Array [6] Option: Function: Option: Function: [53] Drive ready The frequency converter is ready for the motor, the frequency converter, operation and applies a supply signal the brake resistor or thermistor.
  • Page 124 Parameter Descriptions AF-650 GP Programming Guide LC-10 Comparator Operand LC-11 Comparator Operator Array [6] Array [6] Option: Function: Option: Function: [131] Digital input DI19 Digital input 19. High = True. < Select [0] < for the result of the evaluation to...
  • Page 125 Parameter Descriptions AF-650 GP Programming Guide LC-15 RS-FF Operand S LC-15 RS-FF Operand S Option: Function: Option: Function: [16] Thermal warning [96] RS Flipflop 2 [17] Line voltage out of range [97] RS Flipflop 3 [18] Reversing [98] RS Flipflop 4...
  • Page 126 Parameter Descriptions AF-650 GP Programming Guide 3.19.4 LC-4# Logic Rules LC-16 RS-FF Operand R Option: Function: Parameters to configure the Logic Controller (LC) Logic [43] Ok key Rules. Logic Rules are used to define what conditions need [44] Reset key to be met for the LC to step to the next event.
  • Page 127 Parameter Descriptions AF-650 GP Programming Guide LC-43 Logic Rule Operator 2 LC-52 Logic Controller Action Array [6] Array [20] Option: Function: Option: Function: Select the second logical operator to be LC-51 Logic Controller Event) is evaluated used on the boolean input calculated in as true.
  • Page 128 Parameter Descriptions AF-650 GP Programming Guide LC-52 Logic Controller Action LC-52 Logic Controller Action Array [20] Array [20] Option: Function: Option: Function: [14] Select preset ref Selects preset reference 4. [31] Start timer 2 Starts timer 2, see LC-20 Logic Controller If the active preset reference is changed, Timer for further description.
  • Page 129: B-## Brakes

    Parameter Descriptions AF-650 GP Programming Guide 3.20 B-## Brakes B-03 DC Brake Cut In Speed [RPM] Range: Function: Parameter group related to the brake features in the drive. 0 RPM [0 - 60000 Set the DC brake cut-in speed for...
  • Page 130 Parameter Descriptions AF-650 GP Programming Guide B-10 Brake Function B-13 Braking Thermal Overload Option: Function: Option: Function: that AC brake is not as effective as dynamic This parameter is only active in frequency breaking with resistor. converters with an integral dynamic brake.
  • Page 131 Parameter Descriptions AF-650 GP Programming Guide B-15 Brake Check B-17 Over-voltage Control Option: Function: Option: Function: amplitude before braking + 1%: Brake Over-voltage control (OVC) reduces the risk check has failed by returning a warning of the frequency converter tripping due to or alarm.
  • Page 132 Parameter Descriptions AF-650 GP Programming Guide 3.20.3 B-2# Mechanical Brake Parameters for controlling operation of an electro-magnetic (mechanical) brake, typically required in hoisting applications. To control a mechanical brake, a relay output (relay 01 or relay 02) or a programmed digital output (terminal 27 or 29) is required.
  • Page 133 Parameter Descriptions AF-650 GP Programming Guide B-20 Release Brake Current B-23 Activate Brake Delay Range: Function: Range: Function: par. [0 - par. Set the motor current for release of the After setting B-23 Activate Brake Delay the torque drops to zero in few minutes. The sudden torque...
  • Page 134 Parameter Descriptions AF-650 GP Programming Guide Illustration 3.45 Brake release sequence for hoist mechanical brake control I) Activate brake delay: The frequency converter starts again from the mechanical brake engaged position. II) Stop delay: When the time between successive starts is shorter than the setting in B-24 Stop Delay, the frequency converter starts without applying the mechanical brake (e.g.
  • Page 135: Pi-## Pid Controls

    Parameter Descriptions AF-650 GP Programming Guide 3.21 PI-## PID Controls PI-03 Speed PID Integral Time Range: Function: Parameter group related to PID Controls long to regulate errors. This parameter is used with [0] Speed open loop and [1] Speed closed 3.21.1 PI-0# Speed PID Control...
  • Page 136 Parameter Descriptions AF-650 GP Programming Guide NOTE PI-07 Speed PID Feedback Gear Ratio Severe filtering can be detrimental to dynamic Range: Function: performance. [0.0001 - 32.0000] This parameter is used with H-40 Configuration Mode [1] Speed closed loop and [2] Torque control.
  • Page 137 Parameter Descriptions AF-650 GP Programming Guide PI-20 Process CL Feedback 1 Resource PI-32 Process PID Start Speed Option: Function: Range: Function: of the first of these signals. The 0 RPM [0 - Enter the motor speed to be attained as a...
  • Page 138 Parameter Descriptions AF-650 GP Programming Guide PI-38 Process PID Feed Forward Factor PI-45 Process PID Feed Fwd Resource Range: Function: Option: Function: PI-38 Process PID Feed Forward Factor is active No function Select which drive input should be when H-40 Configuration Mode is set to [3] used as the feed forward factor.
  • Page 139 Parameter Descriptions AF-650 GP Programming Guide PI-51 Process PID Feed Fwd Gain PI-63 Process PID Gain Scaled Output Range: Function: Range: Function: [0 - The feed forward is used to obtain the desired [-200 - 200 %] 100] level, based on a well-known signal available. The...
  • Page 140: Sf-# Special Functions

    Parameter Descriptions AF-650 GP Programming Guide 3.22 SF-# Special Functions SF-00 Wobble Mode Option: Function: 3.22.1 SF-## Wobble Function Rel. Freq., Up/ Down The wobble function is primarily used for synthetic yarn Time winding applications. The wobble option is to be installed NOTE in the frequency converter controlling the traverse drive.
  • Page 141 [1 - 1000 s] This parameter determines the wobble sequence period. This parameter can only be changed in stop-mode. Wobble time = t SF-23 Locked Rotor Detection Time [s] down This parameter is available for AF-650 GP only. SF-08 Wobble Up/ Down Time Range: Function: Range: Function: 0.10 s...
  • Page 142: Parameter Lists

    Parameter Lists AF-650 GP Programming Guide 4 Parameter Lists 4.1 Parameter Options 4.1.1 Introduction Changes during operation ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made.
  • Page 143: K-## Keypad Set-Up

    Parameter Lists AF-650 GP Programming Guide 4.1.2 K-## Keypad Set-up Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index K-0# K-01 Language [0] English 1 set-up TRUE Uint8 K-02 Motor Speed Unit [0] RPM 2 set-ups...
  • Page 144 Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index F-03 Max Output Frequency 1 132 Hz All set-ups FALSE Uint16 F-04 Base Frequency ExpressionLimit All set-ups FALSE Uint16 F-05...
  • Page 145: E-## Digital In/Outs

    Parameter Lists AF-650 GP Programming Guide 4.1.4 E-## Digital In/Outs Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index E-0# E-00 Digital I/O Mode [0] PNP All set-ups FALSE Uint8 E-01 Terminal 18 Digital Input...
  • Page 146: C-## Frequency Control Functions

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index E-78 Pulse Output Max Freq #X30/6 5000 Hz All set-ups TRUE Uint32 E-8# E-80 Term 32/33 Pulses Per Revolution 1024 N/A...
  • Page 147: H-## High Perf Parameters

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index P-10 Slip Compensation Time Constant ExpressionLimit All set-ups TRUE Uint16 P-2# P-20 Motor Construction [0] Asynchron All set-ups FALSE Uint8...
  • Page 148 Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index H-48 Clockwise Direction [0] Normal All set-ups FALSE Uint8 H-49 Motor Angle Offset Adjust [0] Manual All set-ups FALSE Uint8...
  • Page 149: An-## Analog In / Out

    Parameter Lists AF-650 GP Programming Guide 4.1.8 AN-## Analog In / Out Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index AN-0# AN-00 Live Zero Timeout Time 10 s All set-ups TRUE Uint8 AN-01 Live Zero Timeout Function...
  • Page 150: Sp-## Special Functions

    Parameter Lists AF-650 GP Programming Guide 4.1.9 SP-## Special Functions Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index SP-0# SP-00 Fault Level ExpressionLimit 1 set-up TRUE Uint8 SP-1# SP-10 Line failure [0] No function...
  • Page 151: O-## Options/Comms

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index SP-89 Decel Time 3 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE Uint8 SP-9# SP-90 Decel Time 3 S-ramp Ratio at Decel. End...
  • Page 152: Dn-## Devicenet

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index O-58 Profidrive OFF3 Select [3] Logic OR All set-ups TRUE Uint8 O-8# O-80 Bus Message Count 0 N/A All set-ups...
  • Page 153: Pb-## Profibus

    Parameter Lists AF-650 GP Programming Guide 4.1.12 PB-## Profibus Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index PB-0# PB-00 Setpoint 0 N/A All set-ups TRUE Uint16 PB-07 Actual Value 0 N/A All set-ups FALSE...
  • Page 154: En-## Ethernet

    Parameter Lists AF-650 GP Programming Guide 4.1.13 EN-## Ethernet Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index EN-0# EN-00 IP Address Assignment ExpressionLimit 2 set-ups TRUE Uint8 EN-01 IP Address 0 N/A 1 set-up...
  • Page 155: Ec-## Feedback Option

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index EN-94 Broadcast Storm Protection -1 % 2 set-ups TRUE Int8 EN-95 Broadcast Storm Filter [0] Broadcast only 2 set-ups TRUE...
  • Page 156: Id-## Drive Information

    Parameter Lists AF-650 GP Programming Guide 4.1.16 ID-## Drive Information Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index ID-0# ID-00 Operating hours All set-ups FALSE Uint32 ID-01 Running Hours All set-ups FALSE Uint32 ID-02...
  • Page 157: Dr-## Data Readouts

    Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index ID-8# ID-80 Fan Running Hours All set-ups TRUE Uint32 ID-81 Preset Fan Running Hours All set-ups TRUE Uint32 ID-9# ID-92...
  • Page 158 Parameter Lists AF-650 GP Programming Guide Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index DR-49 Current Fault Source 0 N/A All set-ups TRUE Uint8 DR-5# DR-50 External Reference 0 N/A All set-ups FALSE Int16...
  • Page 159: Lc-## Logic Controller

    Parameter Lists AF-650 GP Programming Guide 4.1.18 LC-## Logic Controller Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index LC-0# LC-00 Logic Controller Mode ExpressionLimit 2 set-ups TRUE Uint8 LC-01 Start Event ExpressionLimit 2 set-ups...
  • Page 160: B-## Braking Functions

    Parameter Lists AF-650 GP Programming Guide 4.1.19 B-## Braking Functions Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index B-0# B-00 DC Hold Current 50 % All set-ups TRUE Uint8 B-01 DC Brake Current 50 %...
  • Page 161: Pi-## Pid Controls

    Parameter Lists AF-650 GP Programming Guide 4.1.20 PI-## PID Controls Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index PI-0# PI-00 Speed PID Feedback Source ExpressionLimit All set-ups FALSE Uint8 PI-02 Speed PID Proportional Gain...
  • Page 162: Sf-# Special Functions

    Parameter Lists AF-650 GP Programming Guide 4.1.21 SF-# Special Functions Par. No. Parameter description Default value 4-set-up Change Conver- Type during sion operation index SF-0# SF-00 Wobble Mode [0] Abs. Freq., Abs. Time All set-ups FALSE Uint8 SF-01 Wobble Delta Frequency [Hz]...
  • Page 163: Troubleshooting

    Troubleshooting AF-650 GP Programming Guide 5 Troubleshooting If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked 5.1 Status Messages (see also Table 5.1). 5.1.1 Warnings/Alarm Messages Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off before the alarm can be reset.
  • Page 164 Troubleshooting AF-650 GP Programming Guide Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Hardware mismatch Short Circuit Control word time-out O-04 Control Word Timeout Function Temp. Input Error Param Error Internal Fans External Fans Brake resistor short-circuited Brake resistor power limit...
  • Page 165 Troubleshooting AF-650 GP Programming Guide Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Voltage Limit Control Board Over-temperature Heat sink Temperature Low Option Module Configuration has Changed Pwr. Card Temp Illegal Drive configuration Illegal Profile Sel. Power Unit Setup Reduced power mode...
  • Page 166 Troubleshooting AF-650 GP Programming Guide Alarm Word Alarm Word 2 Warning Word Warning Extended Word 2 Status Word 00000080 Motor Th Over reserved Motor Th Over (W11) reserved Output Current (A11) High 00000100 Motor Electronic reserved Motor Electronic OL reserved...
  • Page 167 Troubleshooting AF-650 GP Programming Guide WARNING 1, 10 Volts low Troubleshooting The control card voltage is below 10 V from terminal 50. Connect a brake resistor Remove some of the load from terminal 50, as the 10 V Extend the ramp time supply is overloaded.
  • Page 168 Troubleshooting AF-650 GP Programming Guide Check that the motor current set in P-03 Motor If extended mechanical brake control is selected, trip can Current is correct. be reset externally. Ensure that Motor data in parameters P-02, P-03, Troubleshooting P-06, P-07, F-04 and F-05 are set correctly.
  • Page 169 Troubleshooting AF-650 GP Programming Guide Check the operation of the communication WARNING/ALARM 27, Brake chopper fault equipment. The brake transistor is monitored during operation and if a short circuit occurs, the brake function is disabled and a Verify a proper installation based on EMC warning is issued.
  • Page 170 Check E-57 Term X30/7 Digi Check for loose or missing wiring Out (OPCGPIO). It may be necessary to contact your GE supplier or service ALARM 45, Earth fault 2 department. Note the code number for further trouble- Earth (ground) fault on start-up.
  • Page 171 Troubleshooting ALARM 50, Auto tune calibration failed • Check that the ambient operating temperature is Contact your GE supplier or GE Service Department. within limits • Check for clogged filters ALARM 51, Auto tune check U and I •...
  • Page 172 Troubleshooting AF-650 GP Programming Guide connections from motor – encoder – to frequency converter. Select motor feedback function in H-20 Motor Feedback Loss Function. Adjust tracking error band in H-25 Tracking Error and H-27 Tracking Error Ramping. ALARM 79, Illegal power section configuration The scaling card is the incorrect part number or not installed.
  • Page 173 Index AF-650 GP Programming Guide Freeze Output..................4 Index Fuses....................... 169 Adv. Start Adjust, SF-2#..............140 Graphical Display.................. 13 Advanced Vector Control..............5 Alarm Messages..................162 Word..................... 87 IGMP......................104 Analog Indexed Parameters................21 Input....................166 Indicator Lights..................14 Inputs...................... 5 Signal....................
  • Page 174 Index AF-650 GP Programming Guide Potentiometer Reference..............11 Programming..................166 Warning Word..................87 Protection Mode..................8 Warnings....................162 Pulse Start/Stop..................11 Quick Menu....................14, 18 Menu Mode................. 14, 17 Transfer Of Parameter Settings Between Multiple Frequen- cy Converters..16 Rated Motor Speed................4 RCD.......................
  • Page 175 GE company. AF-650 GP is a trademark of the General Electric Company. 41 Woodford Avenue Plainville, CT 06062 www.geelectrical.com/drives...

Table of Contents