1-2-6. DETAILS OF FUNCTION
 CONTROL INPUT FUNCTION
-1: Operation/Stop mode
●In the case of "Edge" input
Function
Dip-SW
setting
SET2-2: OFF
46-00
(Factory setting)
On
CNA01 or
CNA02
Off
Operation
Indoor unit
Stop
Remote
Controller
●In the case of "Pulse" input
Function
Dip-SW
setting
46-00
SET2-2: ON
Ch1 input
CNA01
or
CNA02
Ch2 input
Indoor unit
Remote
Controller
NOTES :
● The last command has priority.
● The indoor units within the same remote controller group operates in the same mode.
External input
CNA01 or CNA02
(EXT.IN1)
External input
Ch1
CNA01 or CNA02
(EXT.IN1)
Ch2
The width of pulse must be longer than 200 msec.
On
Off
On
Off
Operation
Stop
- (08 - 14) -
Input signal
Command
OFF → ON
Operation
ON → OFF
Stop
On
Input signal
Command
OFF → ON
Operation
OFF → ON
Stop