Fujitsu Airstage J-II Series Design & Technical Manual page 721

Small vrf system
Table of Contents

Advertisement

2-1-4. J-II series
„ SETTINGS LIST
LED105
Setting Mode
CODE No.
Pipe length
0
0
setting
1
0
Prohibited
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
1
4
Prohibited
LED104
Setting Function
CODE No.
Standard (131 to
0
0
213ft.)
(40 to 65m)
Short (less than 131ft.)
0
1
(less than 40m)
Medium (213 to 295ft.)
0
2
(65 to 90m)
Long 1 (295 to 394ft.)
0
3
(90 to 120m)
0
4
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Normal mode
0
1
Save energy mode 1
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
4
Prohibited
- (07 - 74) -
Factory
Remarks
setting
l
Pipe length means the length between outdoor
unit and the nearest indoor unit.
l
Setting prohibited
l
l
l
Setting prohibited
l
Setting prohibited