Fujitsu Airstage J-II Series Design & Technical Manual page 740

Small vrf system
Table of Contents

Advertisement

Case2 : When setting number is two digits.
(11-2) Indoor unit will display the function setting number on "OPERATION"(GREEN), "TIMER
"(ORANGE) and "FILTER "(RED) light.
Phase1
OPERATION
TIMER
(GREEN)
(ORANGE)
Flashing times of
Flashing times of
function numbers
function numbers
(the ten's place)
(the one's place)
The display of "Phase1" and
"Phase2" is alternately repeated.
Phase2
OPERATION
TIMER
(GREEN)
(ORANGE)
OFF
OFF
Number 0 setting will not indicate TIMER LAMP and FILTER LAMP.
¾
z Confirmation of function setting
(12) Press the "TIMER set (+)" button.
"TIMER set (+)"
„ FUNCTION DETAILS
Refer to 2-8. FUNCTION DETAILS.
FILTER
(RED)
Flashing times of
setting numbers
(the one's place)
FILTER
(RED)
Flashing times of
setting numbers
(the ten's place)
PiPi
CORRECT : Pi
PiPiPiPiPi
PiPi
WRONG: Pi
(3 sec)
- (07 - 93) -
(Example) Function number : 26, Setting number : 31
0.5sec ON / 0.5sec OFF
OPERATION LAMP
2 times
(GREEN)
0.5sec ON / 0.5sec OFF
TIMER LAMP
(ORANGE)
0.5sec ON / 0.5sec OFF 0.5sec ON / 0.5sec OFF
FILTER LAMP
1 time
(RED)
(Phase1) : 12sec
...
OFF
6 times
...
OFF
...
3 times
(Phase2) : 12sec

Hide quick links: