Honeywell E-Mon IDR Series Installation Instructions Manual page 23

Interval data recorder
Table of Contents

Advertisement

Appendix F - System Wiring Guides
UP TO 26 IDR-16S PER
CHANNEL
NOTE: METERS 1-16 MUST BE INSTALLED WITHIN 500 FEET OF IDR.
PC
CONNECTS VIA
USB PORT ON PC
IDR A-B
AC ADAPTER
RJ-11
~ ~
IDR Y-Z
AC ADAPTER
CONNECTION
IDR TO METERS 1-16
IDR TO USB KEY
IDR TO RS-232 KEY 2000
RS-232 KEY 2000 TO COMPUTER**
IDR TO PULSE METER
** SUPPLIED BY HONEYWELL
NOTE: INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED
WITH THE PRE-WIRED MMU-TYPE METERING CABINETS.
NOTE: WHEN CONSTRUCTING FIELD-INSTALLED CABLES, MODULAR
CABLES MUST BE MADE SO THAT THE INDIVIDUAL WIRES GO
THROUGH ON THE SAME PIN NUMBER.
* CONTACT HONEYWELL FOR USB-ONLY CONNECTION.
USB
KEY*
RJ-11
4-CONDUCTOR
FLAT MODULAR CABLE
UP TO 4000 FEET TOTAL
DAISY-CHAIN
6-COND.
6-COND.
RJ-45
RJ-45
3RD
3RD
PARTY
PARTY
METER
METER
PAIR OF WIRES
(#22-#14 AWG)
CABLE TYPE
CONNECTOR
6-COND. 22-26 AWG
RJ-45
(PINS 1 & 8 NOT USED)
4-COND. 26 AWG
RJ-11
4-COND. 26 AWG
RJ-11
8-COND. 22-26 AWG
RJ-45/DTE
FLAT MODULAR CABLE
2-COND. 14-22 AWG
23
E-MON INTERVAL DATA RECORDER
(UP TO
16 METERS)
6-COND.
RJ-45
(UP TO 16 METERS)
3RD
PARTY
METER
M37288
62-0394—06