Table 6. Honeywell E-Mon LonWorks Point Map: IDR8 and IDR16. (Continued)
Network Variable
Name
4
nvoStatus
4
nviRequest
nvoFileDirectory
1.?To clear all usage channels, select reset kW/kWh on the display menu of the IDR. Jumper J6 must be closed.
To clear individual channels, set nviResetUsageCh to the desired channel. For example, set nviResetUsageCh to
1 to reset nvoUsageCh01.
2. To set the real time clock, set nviRTC_DateTime to the desired date and time.
3. NvoIntervalData will display the number of pulses for the selected interval period and channel. For example,
set nviIntDataTime to 6/1/2012 13:15:00 to read the number of pulses from 13:15:00 to 13:29:59. The second
status bit value will be 0 if no error has occurred. The interval data period window can be set to read 15 or 5
minutes using the nviIntDataPeriod. This value will not change the default interval data period value of 15
minutes. NviIntDataChan will select the usage channel. For example, set nviIntDataChan to 1 to read the
interval data for nvoUsageCh01.
4. NviRequest commands can disable or enable functional blocks. Any changes will be saved even after
powered down. Set nviRequest to 0,RQ_DISABLE to disable all functional blocks. Set nviRequest to
0,RQ_ENABLE to enable all function blocks. Set nviRequest to 1,RQ_DISABLE to disable only functional block 1.
The first value of nvoStatus is the functional block, and the 3
With an IDR16 each channel 1 through 16 represents the IDR16 meter jack inputs 1 through 16.
With an IDR8 each channel 1 through 8 represents the IDR8 meter jack inputs 1 through 8.
Function
Block Index
SNVT Type
0
SNVT_obj_stat
us
0
SNVT_obj_requ
est
0
SNVT_address File Directory
E-MON INTERVAL DATA RECORDER
Description
Function Block Status
Function Block Request Function Block
rd
bit in the bit array is 1 when disabled.
19
Units
Function Block Status
Enable/Disable
Config File Directory
IDR
R
R/W
R
62-0394—06