E-MON INTERVAL DATA RECORDER
Appendix E - System Wiring Guides
62-0394—06
PC
CONNECTS VIA
USB PORT ON PC
3 FT USB A TO USB B CABLE
IDR A
AC ADAPTER
RJ-11
~ ~
IDR Z
UP TO 52 IDRS
AC ADAPTER
NOTE: METERS 1-8 MUST BE INSTALLED WITHIN 500 FEET OF IDR.
CONNECTION
IDR TO METERS 1-8
IDR TO IDR
IDR TO USB KEY
USB KEY TO COMPUTER**
IDR TO PULSE METER
** SUPPLIED BY HONEYWELL
NOTE: INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED WITH
THE PRE-WIRED MMU-TYPE METERING CABINETS.
NOTE: WHEN CONSTRUCTING FIELD-INSTALLED CABLES, MODULAR CABLES MUST BE
MADE SO THAT THE INDIVIDUAL WIRES GO THROUGH ON THE SAME PIN NUMBER.
* CONTACT HONEYWELL FOR USB-ONLY CONNECTION.
USB
KEY*
RJ-11
4-CONDUCTOR
FLAT MODULAR CABLE
UP TO 4000 FEET TOTAL
DAISY-CHAIN
6-COND.
6-COND.
RJ-45
RJ-45
CABLE TYPE
CONNECTOR
6-COND. 22-26 AWG
(PINS 1 & 8 NOT USED)
4-COND. 26 AWG
4-COND. 26 AWG
3 FT USB A to USB B Cable
2-COND. 14-22 AWG
22
(UP TO 8
METERS)
6-COND.
RJ-45
(UP TO 8
METERS)
RJ-45
RJ-11
RJ-11
RJ-45/DTE
M37287