E3 Series System Connections
Event
Phone Line 2 Fault Restored
Automatic Test (NORMAL)
Automatic Test (With Exception)
For Contact ID and SIA Formats:
GG
= group number assigned to the device, 00-99 (For networked systems, GG = Node number)
= group number assigned to the device, 00-899 (For extended network reporting)
NN
= 00 (standalone systems) or node number (networked systems only)
UUU = User-configured ID code (events originating from SLC devices, if configured) or event type code (non SLC
device events). For more details, see, "3.10.5.1 Reporting Codes for Non-SLC-Device Events".
T
= Type of device or event causing the event to be reported.
0
= Any Device not listed below.
1
= General Alarm Device
2
= Manual Station Alarm
3
= Supervisory Device (Non-latching)
4
= Supervisory Device (Latching)
5
= Waterflow (Non-silenceable)
6
= Smoke Alarm
7
= Non-reporting Device
8
= Multi-level Device
NOTE 1: Special AMM/PIDs include the following functions: Reset Switch, Silence Switch, Drill Switch,
Alarm Acknowledge Switch, Trouble Acknowledge Switch.
NOTE 2: In SIA format, two separate reports are made to transmit the extended codes (if configured).
See Notes 4 and Note 5.
NOTE 3: In 4/1 format, the "one's" digit of the user-assigned code will be reported (if configured).
See Notes 4 and Note 5.
NOTE 4: The standard code format (in brackets) will always be used to report events originating from
7100, INI-VGC, INI-VGX, INI-VGE or NGA nodes.
NOTE 5: The DACT-E3 will report 000 as the "UUU" digits if an event occurs on an SLC device that
does not have a user-configured code assigned to it and the system is configured to report custom
DACT codes. The node number will also be reported.
148
Digital Alarm Communicator Transmitter (DACT-E3) Connections
SIA
(See Note 2
LR 2
RP 0
RP 991
Table 3.10.5.1 DACT-E3 Event Reporting Codes
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Contact ID
3 352 [00] (NN) [000] (UUU) 72
1 602 [00] (NN) [000] (UUU) 90
1 602 [00] (NN) [991] (UUU) 91
4/2
(See Note 3) 3/1
7
9
9