Connect analog DC inputs

The CL-AC1, CL-AC2 and CL-DC2 basic units are provided
with analog inputs. Inputs I7 and I8, and if present I11 and
I12, can be used to connect analog voltages ranging from 0
V to 10 V. A simple additional circuit also allows the analog
evaluation of currents from 0 to 20 mA. The analog input
signals are converted to 10-bit digital signals.
The following signals apply:
• 0 V DC corresponds to a digital 0.
• 5 V DC corresponds to a digital value of 512.
• 10 V DC corresponds to a digital value of 1023.
Connecting the inputs
ON signal
15 to 28.8 V
greater than 8 V DC
15 to 28.8 V
greater than 8 V DC
15 to 28.8 V
ON signal
8 to 15.6 V DC
Input current
3.3 mA at 24 V DC
2.2 mA at 24 V
3.3 mA at 24 V DC
2.2 mA at 24 V
3.3 mA at 24 V DC
Input current
3.3 mA at 12 V
1.1 mA at 12 V
3.3 mA at 12 V
1.1 mA at 12 V
41