CL settings
DEBOUNCE
P BUTTONS
RUN MODE
CARD MODE æ
Setting the cycle time
P BUTTONS
RUN MODE
CARD MODE å
CYCLE-T.. .æ
CYCLE TIME
CYCLE TIME
220
Deactivating card mode
CARD MODE å
åÆ
Select
X
å
The Card mode function is deactivated.
The default setting for the logic relay is for CARD MODE to
be displayed. In other words, the logic relay starts in RUN
mode when the power is switched on.
The logic relay allows you to fix the cycle time. To do this,
move to the SYSTEM menu and from there to the CYCLE
TIME... menu.
h
Factory setting:
The cycle time is set to 00 ms.
The cycle time can only be set in STOP mode.
Æ
The logic relay is in STOP mode.
å
Select CYCLE-T and press OK.
X
The following menu appears:
Press OK.
X
You can now enter the set cycle time.
00 MS
ú í
•
Move between the parameters
• ÍÚ Change value.
Press OK to acknowledge the value: e.g. 35 ms.
X
35 MS
The set cycle time is at least 35 ms. The cycle time can be
longer if the logic relay requires more time for processing the
program.
h
The entry of a set cycle time is only useful in applications
involving two-step controllers or similar functions.
With a cycle time setting of 00 ms, the logic relay will
process the circuit diagram and the program at the fastest
possible speed (see also Inside CL, cycle time).
Set cycle time value range:
between 00 and 60 ms.
1SVC 440 795 M0100
and press OK.