Wiring with the logic relay
A1 EQ
I1
F1
I2
F2
OS
HY
102

Parameter display in RUN mode

Parameter display and parameter set for analog value
comparator in RUN mode with the display of the actual
values:
+
0249
Æ
Actual value, e.g.: analog input
0000
Factor is not used
0350
æ
Actual comparison value, e.g.: constant
0000
Factor is not used
0000
Offset is not used
0025
The switching hysteresis is +/– 25
Resolution of the analog inputs
The analog inputs I7, I8, and on the CL-LMR/CL-LMT I11, I12
have the following resolution.
The analog signal from 0 to 10 V DC is converted to a 10-bit
digital value from 0 to 1023. A digital value of 100
represents an analog value of 1.0 V (exactly 0.98 V).
U [V]
10.0
5.0
0
Figure 47: Resolution of the analog inputs
1SVC 440 795 M0100
512
1023