Value Range Of The Operating Hours Counter - ABB CL Series Applications Manual

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

Wiring with the logic relay
O1
S
001000
#
O:000309
144
Parameter display in RUN mode:
+
Set time in hours
Actual time in hours
#
Contact has not switched.
â
Contact has switched.

Value range of the operating hours counter

The operating hours counter counts in the range from
0 hours up to more than 100 years.
Accuracy of the operating hours counter
The operating hours counter counts in seconds. When the
device is switched off, up to 999 ms can be lost.
Function of the operating hours counter function
block
When the coil of the O operating hours counter is set to 1,
the counter increments its actual value by 1 (basic pulse: 1
second).
If the actual value of the operating hours counter reaches the
setpoint of S, the contact O... switches for as long as the
actual value is greater than or equal to the setpoint.
The actual value is kept stored in the device until the reset
coil RO... is triggered. The actual value is then set to zero.
h
Operating mode change RUN, STOP, power On, Off,
delete program, change program, load new program. All
these functions do not clear the actual value of the
operating hours counter.