Specifications - Maytag Amana PTC A Series Service Instructions Manual

Package terminal, air conditioners & heat pumps
Table of Contents

Advertisement

SPECIFICATIONS

PTC073A**AA
1&3
Voltage
Capacity (BUTH)
7,500/7,400
Amps
Watts
EER
UNIT WITHOUT
ELECTRIC HEATER
2&4
Minimum Circuit Ampacity
CFM
HIGH
LOW
HIGH
LOW
Dehumidification
(pints/hr)
Net Weight
Shipping Weight (approx.
lbs.)
PTH073A**AA
1&3
Voltage
230/208
Capacity (BUTH)
7,400/7,200
Amps
2.5/2.6
Watts
625/610
EER
UNIT WITHOUT
ELECTRIC HEATER
2&4
Minimum Circuit Ampacity
CFM
HIGH
220/215
LOW
175/155
HIGH
235/230
LOW
185/165
Dehumidification
(pints/hr)
Net Weight
Shipping Weight (approx.
lbs.)
NOTES:
1. All 265V models must use Amana
®
brand's subbase (PTSB4**C) or Amana
2. Minimum branch circuit ampacity rating conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5
volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time
delay fuses (included and factory installed on Amana
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F
outdoor coil temperature.
6. Total watts for 15,000 Btuh models; subtract 30 watts for PT12*A**AA and 70 watts for PT07/09*A**AA.
7. Please specify 2-digit heater kW size to complete model number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*A*AA.
6
COOLING DATA (COOLING with ELECTRIC HEAT)
PTC074A**AA
PTC093A**AA
230/208
265
7,500
9,000/8,800
2.5/2.6
2.0
625/610
625
11.6
11.6
4.0
3.3
220/215
220
175/155
175
235/230
235
185/165
185
35
35
1.9
1.9
110
110
130
130
COOLING DATA (HEAT PUMP)
PTH074A**AA
PTH093A**AA
265
7,400
9,000/8,800
2.0
625
11.5
11.5
4.0
3.3
220
175
235
185
35
35
1.9
1.9
110
110
130
130
®
brand's hard wire kit (PTPWHWK4).
®
brand chassis).
PTC094A**AA
PTC123A**AA
230/208
265
9,000
12,200/12,000
3.5/3.8
3.0
810/790
810
11.1
11.1
4.8
4.1
Cool, Wet Coil
220/215
220
175/155
175
Dry Coil
235/230
235
185/165
185
Ventilated Air
35
35
2.7
2.7
120
120
140
140
PTH094A**AA
PTH123A**AA
230/208
265
9,000
12,000/11,600
3.5/3.8
3.0
810/790
810
1,145/1,125
11.1
11.1
4.8
4.1
Cool, Wet Coil
220/215
220
175/155
175
Dry Coil
235/230
235
185/165
185
Ventilated Air
35
35
2.7
2.7
120
120
140
140
PTC124A**AA
PTC153A**AA
230/208
265
12,200
14,200/14,000
4.6/5.0
3.7
1,145/1,125
1,145
10.8
10.8
7.3
5.7
290/270
290
220/190
220
310/290
310
235/205
235
45
45
3.8
3.8
130
130
150
150
PTH124A**AA
PTH153A**AA
230/208
265
12,000
14,000/13,800
4.6/5.0
3.7
1,145
1,490/1,470
10.6
10.6
7.3
5.7
290/270
290
220/190
220
310/290
310
235/205
235
45
45
3.8
3.8
130
130
150
150
EER -
Energy Efficiency Ratio per The Air-Conditioning,
Heating, and Refrigeration Institute (AHRI) Test
Procedures and Canadian Standards Association
(CSA) Test Procedures
COP -
Coefficient of Performance per AHRI Test
Procedures
PTC154A**AA
230/208
265
14,200
7.4/7.9
6.5
1,510/1,490
1,510
9.4
9.4
8.4
7.7
325/315
325
250/220
250
345/335
345
265/235
265
50
50
4.4
4.4
140
140
160
160
PTH154A**AA
230/208
265
14,000
7.4/7.9
6.5
1490
9.4
9.4
8.4
7.7
325/315
325
250/220
250
345/335
345
265/235
265
50
50
4.4
4.4
140
140
160
160

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amana pth seriesAmana pth m seriesAmana ptc073a aa seriesAmana pth z seriesAmana pth r seriesAmana ptc074a aa series ... Show all

Table of Contents