Configuration Settings - Maytag Amana PTC A Series Service Instructions Manual

Package terminal, air conditioners & heat pumps
Table of Contents

Advertisement

PROPER INSTALLATION
Feature Code
---
Start Configuration position
C1
Interface Usage
C2
Fan Operation
C3
Reverse Cycle Operation
C4
Room Identification first two digits
C5
Room Identification last two digits
C6
Wired Occupancy
C7
Wired Motion Sensor Type
C8
Cooling Temperature Limiting
C9
Heating Temperature Limiting
C0
Reverse Cycle "B" or "O"
selection for thermostat
c2
Wired Unrented Set Back
c3
Unrented Cooling Temperature
c4
Unrented Heating Temperature
Cb
Dehumidification
CC
Dehumidistat call for a drop in temperature
Cd
English/Metric Temperature
CE
Freeze Protection
CF
Hi. Speed Cooling Smart Temperature
CH
Hi Speed Heating Smart Temperature
CJ
2nd Stage Heat. Dif.
d1
Room Air Mix Cooling
d2
Room Air Mix Heating
d3
Air Mix Fan Speed
d4
Heating Smart Speed
d5
Warnings,
OCT Lock & LED
d6
Sensorless Un-Occ. Time and Fan Revert Time
d7
1st Un-Occ. Set Back Temperature
d8
1st Un-Occ. Set Back Time
d9
2nd Un-Occ. Set Back Temperature
dA
2nd Un-Occ. Set Back Time
dB
3rd Un-Occ. Set Back Temperature
dC
3rd Un-Occ. Set Back Time
dH
Electric Heater Size
r4
Room Prefix
r5
Room Suffix
*Indicates factory default.
32
Description
Option Code

CONFIGURATION SETTINGS

Unit is only controlled by the PTAC touchpad.
0*
rE
Unit is both controlled by a wireless thermostat and/or the touchpad.
L5
Unit is controlled by a wired thermostat via the low voltage terminals only.
The fan only runs with the call for heating or cooling.
Au*
The fan runs continuously except in the OFF position.
On
The fan runs continuously in cooling and cycles with call for heating.
C
Unit is equipped with fan operation button for guest selection of fan cycling.
bP
Unit is equipped with fan operation button, but self reverts to cyclic fan.
bA
Unit is equipped with fan operation button, but self reverts to continuous fan.
bC
The fan always runs even in OFF mode
A
Cooler only with or without electric heat.
C
Heat Pump.
H*
Service no Operation "Eo"
0
Set first two digits of room identification
00-99
Set last two digits of room identification
00-99
"No Occupancy" detection devices
0*
Wired Door Switch and Motion Sensor present
1
18
Enter "No Occupancy" routine 18 hours after last control selection
Normally Closed Device (Open when sensing motion)
0*
Normally Open Device (Closed when sensing motion)
1
Select temperature between 60 and 72 for minimum cooling set point
60*-72
Select temperature between 68 and 90 for maximum heating set point
68-90, 80*
Mating thermostat has a "B" terminal
8*
Mating thermostat has an "O" terminal
0
Not Active
0*
Active
A
Select temperature between 45 and 95 minimum unrented cooling set point.
45-95, 79*
Select temperature between 45 and 95 minimum unrented heating set point.
45-95, 63*
Not Active
0*
Active
1
Active in No occupancy / Unrented State
U
3-8
3-8
Fahrenheit Scale
F*
Celsius Scale
C
On, low fan*
L*
On, high fan
H
Off
0
5-9
5*-9
6-8
6-8*
4-8
4*-8
No electric heat
--
On
1*
Off
0
Off
0*
On
1
Low
L*
High
H
Not Available
0
Available
1*
Enabled
1*
Dis-enabled
0
1- 32, 18*
1-32
1-16, 2*
1-16
.1, .5, 1-24, .5*
.1, .5, 1-24
1-16, 3*
1-16
.1, .5, 1-24
(d8)-24, 1*
1-16, 6*
1-16
(dA)-24, 3*
.1, .5, 1-24
00*, 15, 20,
00*, 15, 20, 25, 35 & 50
25, 35, 50
00* - 99
00* - 99
00* - 99
00* - 99
Description