Honeywell ControLinks S7999 Product Data page 8

Display module

Advertisement

S7999 CONTROLINKS™ DISPLAY MODULE
Selectable Message/Display
Total Cycles
Run Time
Inputs/Outputs:
CmA
ManPot
XmA
XmA Temp
Current Fuel
F2(1) Position
Manual
T4
FSelect1
T5
FSelect2
T6
Alarm
T7
HFP
T8
LFP
T9
HF
T10
MV
T11
LF
T12
LCI
T13
LCO
T14
Motor Settings
Lightoff
F1(2)
Lightoff
Air
Lightoff
FGR
Purge
F1(2)
Purge
Air
Purge
FGR
Prog Stop
F1(2)
Prog Stop
Air
65-0262
Table 3. Selectable Messages.
Description
Total number of equipment
operating cycles
Total number of equipment
operating time (hours:minutes)
Top-level prompt for diagnostic
information.
Controller Input
Manual Potentiometer
Auxiliary Input
Auxiliary Input
Current fuel selected.
Fuel actuator position for
currently inactive fuel.
Manual/Auto Input
Fuel 1 Input
Fuel 2 Input
Alarm Output
High Fire Proven Output
Low Fire Proven Output
High Fire Input
Main Valve Input
Low Fire Input
Limit/Control Input
Limit/Control Output
Top level prompt for motor
setting information.
Indicates fuel actuator
programmed position during
Lightoff.
Indicates air actuator
programmed position during
Lightoff.
Indicates FGR actuator
programmed position during
Lightoff.
Indicates fuel actuator
programmed position during
Purge.
Indicates air actuator
programmed position during
Purge.
Indicates FGR actuator
programmed position during
Purge.
Programmed stop of actuator. 00% to 100
Programmed stop of actuator. 00% to 100
Possible States/Range
0 to 999999
0:00 to 999999:00
4.0 to 20.0 mA
4.0 to 20.0 mA
4.0 to 20.0 mA
-40°F to +1400°F
Fuel 1 or Fuel 2
00% to 100%.
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
00% to 100%
00% to 100%
00% to 100%
00% to 100%
00% to 100%
00% to 100%
8
Comments
Cycle will be updated each time main
valve is energized.
Hours:minutes will be updated while
main valve input is energized.
Press the Change Level button to
enter the submenu.
Firing Rate input.
Manual control potentiometer.
Temperature sensor input current.
Temperature sensor input in degrees
Fahrenheit.
The fuel selection as determined at
ControLinks™ System startup.
Either F2 or F1 will be shown,
whichever is the inactive fuel.
ON indicates Manual is selected; OFF
indicates Auto is selected.
Press the Change Level button to
enter the submenu.
Either F1 or F2 will be shown,
whichever is the active fuel.
Either F1 or F2 will be shown,
whichever is the active fuel.
Either F1 or F2 will be shown,
whichever is the active fuel.