Download Print this page

Installation - Honeywell ControLinks S7999 Product Data

Display module

Advertisement

INSTALLATION

WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect the power supply before beginning
installation to prevent electrical shock and equipment
damage. More than one power supply disconnect can
be involved.
When Installing This Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
5. Be sure wiring complies with all applicable codes,
ordinances and regulations.
6. See Fig. 5, 6 and 7 for S7999 unique wiring
connections.
IMPORTANT
1. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, can cause
interference to radio communications. It has been
tested and found to comply with the limits for a Class
B computing device of Part 15 of FCC rules which
are designed to provided reasonable protection
against such interference when operated in a
commercial environment. Operation of this
equipment in a residential area can cause
interference, in which case, users, at their own
expense, can be required to take whatever
measures are required to correct this interference.
2. This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in
the Radio Interference Regulations of the Canadian
Department of Communications.
Humidity
Install the S7999 where the relative humidity never reaches
the saturation point. The S7999 ControLinks™ is designed to
operate in a maximum 85% RH continuous, noncondensing,
moisture environment.
Vibration
Do not install the S7999 where it can be subjected to vibration
in excess of 0.5G continuous maximum vibration.
S7999 CONTROLINKS™ DISPLAY MODULE
Weather
The S7999 is not designed to be weather tight. If installed
outdoors, the S7999 must be protected by an approved
weather-tight enclosure such as the 204718A or 204718C
NEMA 4 Enclosure listed in Accessories.
Remote Mounting DM
The DM can be mounted either on the face of a panel door or
on other remote locations. See Fig. 2. When mounting the DM
on the face of a door panel, closely follow these instructions:
Fig. 2. Panel mounting of a display module.
1. Select the location on the door panel for flush mounting.
2. Pay attention to the insertion dimensions of the two DM
screws, two interlocking ears, and the two plug-in
connections to allow for sufficient clearance.
3. Use the DM or Data ControlBus Module™ as a template
(Fig. 16) and mark the two screw locations, interlocking
ear locations and the two plug-in connector locations.
4. Drill the pilot holes for the mounting screws.
5. Cut holes in the door panel for the interlocking ears and
the two plug-in connectors.
6. Mount the DM, securing it with the two screws provided
in the DM bag assembly.
Use the 203765 Remote Display Mounting Bracket when
mounting the DM on a wall or remote location:
1. Use the 203765 Remote Display Mounting Bracket as a
template to mark the four screw locations.
2. Drill the pilot holes for the four mounting screws.
3. Mount the 203765 Remote Display Mounting Bracket by
securing the four no. 6 screws (M3.5 x 0.6).
See Fig. 3.
4. Mount the DM by aligning the two interlocking ears with
the two mating slots on the remote mounting bracket.
5. Insert the two interlocking ears into the two mating slots.
6. Push on the lower corners of the DM to secure it to the
remote mounting bracket.
7. Make sure the DM is firmly in place.
3
65-0262

Advertisement

loading