Safety Information; General Safety Information; Safety Information As Per En60730-1 - Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions

Table of Contents

Advertisement

LION System

Safety Information

General Safety Information

When performing any work (installation, mounting, start-
up), all instructions given by the manufacturer and in
particular the safety instructions provided in these
Installation and Commissioning Instructions are to be
observed.
The LION System (including the CLLIONLC01, I/O
modules, manual disconnect modules, and the auxiliary
terminal packages) may be installed and mounted only
by authorized and trained personnel.
Rules regarding electrostatic discharge should be
followed.
If the LION System is modified in any way, except by the
manufacturer, all warranties concerning operation and
safety are invalidated.
Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding.
Use only accessory equipment which comes from or has
been approved by CentraLine.
It is recommended that devices are to be kept at room
temperature for at least 24 hours before applying power.
This is to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
The LION System must be installed in such a manner
(e.g., in a lockable cabinet) as to ensure that uncertified
persons have no access to the terminals.
Safety Information as per
EN60730-1
Purpose
The LION System is an independently mounted electronic
control system with fixed wiring.
It is used for the purpose of building HVAC control and is
suitable for use only in non-safety controls for installation on
or in appliances.
Pollution degree
Overvoltage
category
Rated impulse
voltage
Automatic action
Software class
Ball-pressure test
temperature
Electromagnetic
interference
System transformer Europe: safety isolating
Table 1
System data as per EN60730-1
3
Pollution Degree 2,
suitable for use in residential
controls, commercial controls,
in a clean environment.
Category II
for mains-powered (16A) controls
Category I
for 24 V powered controls
2500 VAC
Type 1.C
(micro-interruption for the relay
outputs)
Class A
75 °C for all housing and plastic
parts
125 °C in the case of devices
applied with voltage-carrying parts
and connectors
Tested at 230 VAC,
with the modules in normal
condition.
transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers
EN1Z-0921GE51 R0709

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents