Description of the I/O Modules

Floating Output Module

Features
• Type: CLIOPR825A Floating Output Module
• Housing: light gray
• Floating outputs sufficient for driving up to 3 floating
actuators
• Manual overrides and 3 corresponding pairs of status
LEDs
In the event of communication problems, the 3 floating
outputs will move to the safety positions you have
configured using the engineering tool, see floating output
point description in the CARE – User Guide, 74-5587/EN2B-
0182GE51.
1
3
Fig. 80
CLIOPR825A Floating Output Module with
terminal socket
Legend
1
Service button S1
2
Hex switch S2
3
Manual overrides
4
Status LEDs
4
Service LED
5
Power LED
Functionality of service LED and power LED: see Table 77
to Table 79 on page 78 and following.
EN1Z-0921GE51 R0709
2
4
5 6
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired within
the same relay block.
Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross
connectors must be used, see Table 5 on page 7.
NOTICE
Risk of malfunction!
Cross connectors may only be used if the same voltage
is used on all relays they connected.
Do not use a cross connector if different voltages are
used on the relays.
E.g., use a short cross connector for relay block 1 with
line voltage and no cross connector for relay block 2 with
12 V low voltage for relay 4 and 24 V low voltage for
relays 5 and 6.
Permissible loads
Max. load
Per relay
19...250 VAC
output
current at cos φ ≥ 0.6: 12 A
module (total)
1...29 VDC
12 A resistive, 3 A inductive
Per normally
19...250 VAC
open contact
current at cos φ ≥ 0.6: 4 A)
1...29 VDC
4 A resistive, 1 A inductive
Per normally
19...250 VAC
closed
current at cos φ ≥ 0.95: 2 A,
contact
current at cos φ ≥ 0.6: 1 A
1...29 VDC
4 A resistive, 1 A inductive
Table 57 Permissible loads of floating output modules
Notes
• In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching
more often than once every 2 minutes, these com-
ponents must be prevented from causing harmful
interference to radio or television reception (conformance
with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
58
LION System
Min. load
50 mW
50 mW