The ToxyPoint gas monitor provides continuous monitoring for carbon
monoxide (CO) hazards in ambient air. The monitor is a 2-wire, 4-20mA
transmitter with sensor. It is factory calibrated and tested and has a
maximum operating life of 3 years.
Safety Information
Users of the ToxyPoint require a full understanding of the installation,
operating and maintenance instructions, otherwise protection provided
by the monitor may be impaired. Read the following Warnings before
using the monitor.
Install according to local electrical regulations and codes.
Installation should be performed by qualified personnel.
Do not paint over the sensor screen.
Do not activate the monitor after the date on the package.
Make sure the sensor screen is free of dirt and debris.
Make sure the sensor screen is not covered.
Do not expose the monitor to electrical shock and/or continuous
mechanical shock.
Do not expose the sensor to high pressure water spray.
Do not use the monitor if it is damaged. Before use inspect the
monitor. Look for cracks, missing metals or plastics. If the monitor is
damaged, contact Vulcain immediately.
The warranty will be voided if the customer or any unauthorized
service personnel attempts to repair the unit.
The ToxyPoint should be interfaced to a Class 2 or Limited circuit.
511407
6/07

Introduction

A limited circuit is a circuit supplied by sources such as a battery or a
transformer winding where the open-circuit potential is not more than 30
V r.m.s or 42.4 V.d.c., and the energy available to the circuit is limited
according to one of the following:
The current under any condition of load, including short circuit, is not
more than 8A measured after 1 minute of operation;
The source is RATED or set to limit its power output to 150 VA under any
condition of load including short circuit;
An overload protector or circuit component opens to interrupt the power
output at a lower value than 150 VA under any condition of load including
short circuit.