Honeywell ToxyPoint User Manual page 25

Gas detection device
Table of Contents

Advertisement

Available languages

Available languages

Supply voltage
Power consumption
Operating temperature
Operating humidity
Loop resistance
Output current
Detector
Alarm outputs:
Alarm setpoints
Maximum operating life
Shelf life
Detection range
Visual indicator
Sensor type
Detection technique
Cable
Pollution category
Installation category
Dimensions (DxWxH)
Weight
Certifications
511407
6/07
Specifications
10-28 Vdc (24 Vdc nominal)
50 mA minimum (with no alarm outputs)
24 mA @24 Vdc maximum
4 mA@24 Vdc nominal
0- 50 ºC (32-122 ºF)
15-90% RH (non-condensing)
650 Ohms maximum
Normal operation: 4-20 mA
Fault: 2 mA signal
Sensor expired: 2 mA signal
Over range: 24 mA signal (maximum)
4-20 mA transmitter c/w CO sensor
O/P1 (low alarm), O/P2 (high alarm)
0.25 A outputs activated by low and high gas
alarms and fault alarm
Each alarm not to exceed 250 mA @ 24Vdc
25 ppm and 200 ppm OSHA standard (special
setpoints available)
3 years
1 year
0-500 ppm
Red LED
Electrochemical cell
Instantaneous alarm
2-wire 18-24 AWG
2
I
3.5 x 4.5 x 6.5 cm (1.36" x 1.75" x 2.56")
38 g (1.34 oz.)
IEC No. 61010 (International Electrical Code)
ANSI/ISA S82.01
C22.2 No. 1010 (CS EC)
CSA File LR80259
ToxyPoint User Manual
Honeywell
Specifications