Honeywell 7800 Series Installation Instructions Manual page 16

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7897A1002, RM7897C1000 7800 SERIES RELAY MODULES
Table 8. Blinking Fault Codes and Recommended Troubleshooting. (Continued)
Fault Code
System Failure
Code 4-4
The configuration
*Configuration
jumpers differ from the
Jumper
sample taken at startup.
Problem*
Code 5-1
Preignition Interlock
*Preignition
fault.
Interlock*
Code 5-2
Either High Fire Switch
*High Fire Sw.
or Low Fire Switch
or Low Fire
failure.
Sw.*
Code 5-3
Man-Open Switch, Start
*Man-Open
Switch or Control On in
Sw.; Start Sw.
the wrong operational
or Control On*
state.
Code 6-1
Relay Module self-test
*Internal Faults*
failure.
Code 6-2
Relay Module Self-Test
*Internal Faults*
failure.
Code 6-3
Fault with special OEM
*Device
input circuits.
Specific*
Code 6-4
Unused at this time.
*Accessory
Fault*
Code 7-7
Unused at this time.
*Unused*
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2005 Honeywell International Inc.
66-1151
G.R. 03-05
1. Inspect the jumper connections. Make sure the clipped jumpers were
completely removed.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
1. Check wiring and correct any errors.
2. Check Preignition Interlock switches to assure proper functioning.
3. Check fuel valve operation.
4. Reset and sequence the relay module; monitor the Preignition Interlock status.
5. If the fault persists, replace the relay module.
1. Check wiring and correct any errors.
2. Reset and sequence the relay module.
3. Use manual motor potentiometer to drive the motor open and closed. Verify at
motor switch that the end switches are operating properly. Use RUN/TEST
switch if manual potentiometer is not available.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.
1. Check wiring and correct any errors.
2. Make sure that the Manual Open Valve Switch, Start Switch and Control are
operating properly.
3. Stat Switch held "On" too long.
4. Reset and sequence the relay module.
5. Reset and sequence the relay module. If the fault persists, replace the relay
module (RM7838A1014; RM7838B1013 or RM7838C1004 only).
1. Reset and sequence the relay module.
2. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
3. If the fault persists, replace the relay module.
1. Reset and sequence the relay module.
2. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
3. If fault does not repeat on the next cycle, check for electrical noise being
copied into the relay module through the external loads or possibly an
electrical grounding issue.
4. If the fault persists, replace the relay module.
1. Check wiring and operation of special OEM inputs.
2. Reset and sequence the relay module.
3. If fault reappears, remove power from the device, reapply power, then reset
and sequence the relay module.
4. If the fault does not repeat on the next cycle, check for electrical noise being
copied into the relay module through the external loads or possibly an
electrical grounding issue.
5. If the fault persists, replace the relay module.
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
Recommended Troubleshooting