Function
I/O bytes: the programmer can choose the data to be
transferred.
460/465 basic I/O
460/465 standard I/O
480 basic I/O
480 standard I/O
Baud rate: up to 1500 kbit/s.
The max. range per segment depends on the baud rate:
Baud rate [kbit/s]
93.75
187.5
500
1500
The specified ranges may be increased by using repeat-
ers. No more than three repeaters should be connected
in series.
The specified ranges relate to bus cable type A (two-
core, shielded and twisted), e.g.
Siemens, Order No.: 6XV1830-0EH10, or
Lapp cable unitronic, Order No.: 2170-220T.
BCU 460, BCU 465 · Edition 03.16l
Inputs
Outputs
1 byte
1 byte
4 bytes
1 byte
1 byte
1 byte
5 bytes
1 byte
Range [m]
1200
1000
400
200
33