Power Connections
The AC power supply input option is a Table I selection in the model selection guide. Depending on which
power supply selection is ordered for your actuator, wire the power input (MAINS POWER) as described
in Table 3 and Figure 13. Wiring must confrom to national and local electrical codes
CE Wiring
The CE approval option is a Table IV selection in the model selection guide. When wiring the actuator
power input for CE approved units, you must also install a MOV assembly to the power input. MOV
assembly is ordered as a kit. See Section 8 for kit descriptions and part numbers.
Input Signal Connections
ATTENTION
Shielded and grounded cables are recommended.
0/4-20 mA Input Signals
For current signal input, use the 250 ohm resistor supplied across terminals 28 and 29 on the actuator
terminal block connections. Observing polarity, connect the signal input wires to terminals 28 and 29 of
the terminal block. See Figure 13.
0/1-5 Vdc and 0 to 10 Vdc Input Signals
For voltage signal input, remove the resistor from terminals 28 and 29 on the actuator terminal block.
Observing polarity, connect the signal input wires to terminals 28 and 29 of the terminal block.
Output Signal Connections
0/4-20 mA, 0/1-5 Vdc Feedback Signal Connections
ATTENTION
Shielded and grounded cables are recommended.
Actuator output is 0/4 to 20 mA analog signal. If a voltage input is required for customer devices, a range
resistor is needed at the device input. See Table 3 and Figure 13 for more information.
Slidewire Emulator Connections
ATTENTION
Shielded and grounded cables are recommended.
Slidewire Emulation output option is a Table II selection in the model selection guide. If you ordered the
Slidewire output option for your actuator, it is set at the factory to provide an output that emulates 100 to
1000 ohm slidewires. For terminal block connections to the actuator, refer to Table 3 and Figure 13.
Revision 5
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual
7/07
3. Installation - Electrical Installation