NXS PID Control

What You Need to Know
Motor nameplate data
− Nominal Current
− Nominal Speed
Setup
1 Run the Start Up Wizard
Automatically activated at 1
to Yes and cycle the main power.
Step
Question
Basic Settings
1
Language
2
Application
Application Settings
3
Min. Frequency
4
Max. Frequency
5
Acceleration Time
6
Deceleration Time
Motor Settings
7
Nom. Voltage for the motor
8
Nom. Frequency for the motor Check motor nameplate
9
Nom. Speed for the motor
10
Nom. Current for the motor
Motor Cos ϕ
11
PID and Sensor Settings
12
PID Reference
13
Actual Input
2 Other Control Signal Settings
2 – 10 V: change the value of P2.2.16 AI1 signal range to 20 – 100 %
0 – 20 mA: change the value of P2.2.21 AI2 signal range to 0 – 20 mA
3 PID reference from keypad (if no external reference signal)
R3.4 PID reference value (set-point value in percentage)
% = ((set-point – minimum) / span) x 100
For example: set-point is 3.2 bar, the sensor span is 0 – 5 bar.
3.2 divided by 5 is 0.64; the value to set in P3.5 is thus 64
16
Проектирование. Монтаж. Продажа. - http://vskd.ru
Signal/sensor specification
− Signal type (volts, milliamps)
− Range (0-10, 2-10, 0-20, 4-20)
− Sensor span
st
start. To restart the wizard, set P6.5.3 Start Up Wizard
Recommendation
English
PID Control
20 Hz
50 Hz
30 s for Fan, 15 s for Pump
30 s for Fan, 15 s for Pump
Check motor nameplate
Check motor nameplate
Check motor nameplate
Check motor nameplate
Keypad reference
mA signal: AI2
V Signal: AI1
Fieldbus
mA signal: AI2
V signal: AI1
Note
Typical for Fan or Pump
Typical for Fan or Pump
Default typically OK
Default typically OK
Critical
Critical
Default typically OK
No controller
Signal from controller
Default: 4 – 20 mA
Default: 0 – 10 V