Input and Output Functions
Only DIN3 is programmable in Basic application. If the other functions are required, change
the application to Standard from System Menu (S6.2 Application selection).
DIN1
Start Forward
DIN2
Start Reverse
DIN3
External Fault
Manual Testing
1 Hold LEFT down for 3 seconds
Control Place automatically switches to Keypad
2 Use normal keypad buttons for speed control
• UP and DOWN to adjust the speed
• START and STOP for control
3 Hold LEFT down for 3 seconds to return to remote control (I/O or Fieldbus)
Parameter List
This is the list of the basic parameters that is the only group visible when the Basic
application is selected (in addition to Keypad and System Menu, which are always
visible).
Code
Parameter
P2.1
Min. frequency
P2.2
Max. frequency
P2.3
Acceleration time
P2.4
Deceleration time
P2.5
Current limit
P2.6
Motor nominal voltage
P2.7
Motor nominal frequency
P2.8
Motor nominal speed
P2.9
Motor nominal current
P2.10 Motor Cos ϕ
*
In 230 V series this is 230 V and in 690 V series this is 690 V.
Проектирование. Монтаж. Продажа. - http://vskd.ru
DIN4
Preset Speed 1
DIN5
Preset Speed 2
DIN6
Fault reset
Default
Code
Parameter
0 Hz
P2.11 Start function
50 Hz
P2.12 Stop function
3.0 s
P2.13 U/f optimization
3.0 s
P2.14 I/O reference
I
P2.15 Current reference offset
L
400 V*
P2.16 Analogue output function Output Freq.
50 Hz
P2.17 DIN3 function
1440
P2.18 Preset speed 1
I
P2.19 Preset speed 2
H
0.85
P2.20 Automatic restart
DO1
Ready
RO1
Run
RO2
Fault
Default
Ramp
Coasting
Not used
AI1
Offset 4-20 mA
External Fault
0 Hz
50 Hz
Disabled
15