Honeywell NX Series Pocket Programming Manual page 11

Hvac
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Manual Testing
1 Hold LEFT down for 3 seconds
Control Place automatically switches to Keypad
2 Use normal keypad buttons for speed control
• UP and DOWN for adjusting the speed
• START and STOP for control
3 Hold LEFT down for 3 seconds to return to remote control (I/O or Fieldbus)
Parameter List
This is the list of the most commonly used parameter group: HVAC parameters. Default
values on the list equal the values if Start Up Wizard selection has been FAN or PUMP.
Code
Parameter
P2.1.1
Min. frequency
P2.1.2
Max. frequency
P2.1.3
Accel. time 1
P2.1.4
Decel. time 1
P2.1.5
Current limit
P2.1.6
Motor nominal current
P2.1.7
Motor nominal speed
P2.1.8
Start function
P2.1.9
Stop function
P2.1.10
Automatic restart
P2.1.11
Motor nominal voltage
P2.1.12
Motor nominal frequency
P2.1.13
Preset speed 1
P2.1.14
Parameter conceal
*
Start mode where Tripless Output Switching is enabled.
Проектирование. Монтаж. Продажа. - http://vskd.ru
Unit
Default
FAN
PUMP
Hz
20
20
Hz
50
50
S
20.0
5.0
S
20.0
5.0
A
1, 1xl
L
A
I
Value set in Start Up Wizard
L
Rpm
1440
Value set in Start Up Wizard
2
0 = Ramp
1 = Flying Start
2 = Conditional Flying Start*
0
0 = Coasting
1 = Ramp
0
0 = Not used
1 = Used (3x for automatic Restart)
V
400
Hz
50.00
Hz
10.00
1
0 = All parameters and menus visible
1 = HVAC group P2.1 visible
Note