Flame Signal Measurement - Honeywell 7800 SERIES Instruction Manual

Relay modules
Hide thumbs Also See for 7800 SERIES:
Table of Contents

Advertisement

EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
changed after the 200 hours occur, the relay module locks out.
This safety function assures that the relay module cannot be
modified after it is installed in a particular location.
SERVICE NOTE:Clipping and removing a site-configurable jumper enhances the level of safety.
RESET
BUTTON
DUST
COVER
Fig. 5. EC/RM7830A and EC/RM7850A Relay Modules exploded view.
RUN/TEST SWITCH
Fig. 6. Selectable site-configurable jumpers.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
RUN/TEST
SWITCH
RELAY
MODULE
CONFIGURATION
JUMPERS
PURGE
TIMER
SEQUENCE
STATUS
LED PANEL
SELECTABLE CONFIGURATION
JUMPERS
M7701B
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
66-1092—06
Printed in U.S.A.
honeyvell.energy
If JR3 (Airflow Switch) is intact (no Airflow Switch), then a
jumper must be installed between terminals 6 and 7. If JR3 is
clipped (Airflow Switch is present), the relay module locks out
if it detects a jumper between terminals 6 and 7.
WIRING
SUBBASE
HO NE YW EL L
Table 7. Site-configurable jumper options.
Jumper
Number
Description
JR1
First Safety Time
JR2
Main Trial Time
JR3
Airflow Switch
a
EC7850A1148 or RM7850A1035
Intact—3 seconds Clipped—2 seconds
IMPORTANT
Clipping site-configurable jumpers after 200 hours of
operation results in a nonresettable Code 110,
LOCKOUT. The relay module must be replaced.

Flame Signal Measurement

Measure the flame signal at the appropriate times as defined
in the applicable flame amplifier specifications.
M.S. Rev. 07-11
CAPTIVE
MOUNTING
SCREW
FLAME
AMPLIFIER
M15187A
Intact
Clipped
a
a
5 seconds
3 seconds
5 seconds
3 seconds
No
Yes

Advertisement