Honeywell H-S81-HS Operation Manual page 89

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules
2.4.16 S81-F7008-1
Status Indications
The front panel includes 8 LEDs with the following functions:
Configuration
Thanks to the configuration program ProS81, the following parameters can be set for each load
cell:
Parameter
Operating mode
Pre-alarm threshold
Alarm threshold
Alarm indication mode
Enable/Disable status export to Hosts
Enable/Disable commands from Hosts
on the channel
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Description
This module, used together with S81-MOD-BIL cylinder weighing modules,
allows to monitor cylinder load status and to signal even the slightest extinguish-
ing gas leakage without delay.
Technical Features
• Redundancy:
• Operating modes:
• Interface to field devices:
• Load cells on bus:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
LED
Indication
ACTIVE
Flashing in case of pre-alarm. On Steady in case of load cell alarm.
DISABLED
Steady on if a load cell is disabled.
FAULT
Flashing in case of load cell trouble
MASTER
Not used (steady light)
TX RS232
Not used (off)
RX RS232
Not used (off)
TX RS485
It lights up every time data are transmitted on the RS45 port.
RX RS485
It lights up every time data are received on the RS45 port.
Type
Mode
Sensors
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Sensors
1-3000 hg
Sensors
1-3000 hg
Sensors
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Sensors
No, TCP1, TCP2, RS232
Sensors
No, TCP1, TCP2, RS232
Parts of the H-S81-HS System
No
Master/Slave.
RS485
32
22-29VDC
14mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
89