I/O modules
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of
the single devices, according to the relevant type:
Parameter
Operating mode
Sensitivity
Polling priority for call points
Unit of measure of the channel Sensors
Zero Point
End of scale
Pre-alarm threshold
Alarm threshold
Lower trouble threshold
Type of indication
Automatic alarm reset
Operating mode
Timing
Output type
Polling LED
Enable/Disable status export to
Hosts
Enable/Disable commands
from Hosts on the channel
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Type
Mode
Sensors
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-NC
Sensors
5 or 9 sensitivity levels to be selected
Sensors
Normal, High
Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
Sensors
-500 - 500
Sensors
-500 - 500
Sensors
-500 - 500
Sensors
-500 - 500
Sensors
1.0 - 3.8mA
Sensors
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Sensors
Yes/No
Actuators
Continuous-Normally Energized, Continuous-Normally De-energized,
Intermittent, Pulsing
Actuators
1 to 15 seconds (only for pulsing and intermittent modes)
Actuators
Normal / Sounder
Sensors/Actuators Enable/Disable LED lighting up during polling
Sensors/Actuators No, TCP1, TCP2, RS232
Sensors/Actuators No, TCP1, TCP2, RS232
S81-E2001-1 Bus
The module is connected to a S81-T8003-1 termination module with 8 termi-
nals with a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block with the S81-CCT4 4-conductor
multi-polar cable.
Parts of the H-S81-HS System