Honeywell JADE W7220 Product Data page 5

Economizer module
Table of Contents

Advertisement

1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
1/2 (13)
ONE TERMINAL.
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
Fig. 4. Attaching two or more wires at terminal blocks.
Economizer Module Wiring Details
The wiring connection terminals for each module/sensor are:
• "JADE™ Economizer Module Wiring" on this page.
• "Sylk Bus Sensor Wiring" on page 6.
JADE™ Economizer Module Wiring
Use Fig. 5 and Tables 1 and 2 to locate the wiring terminals for
the Economizer module.
NOTE: The four terminal blocks are removable. You can slide
out each terminal block, wire it, and then slide it back
into place.
JADE CONTROLLER
LEFT TERMINAL
BLOCK LABEL
Fig. 5. W7220 Economizer module terminal connection
M24382
RIGHT TERMINAL
BLOCK LABEL
M32283
labels.
Table 1. Economizer Module - Left hand terminal blocks.
Label
Type
Top Left Terminal Block
MAT
20k NTC
MAT
and
COM
OAT
20k NTC
OAT
and
COM
S-BUS
SYLK Bus Sylk Bus sensor
S-BUS
Bottom Left Terminal Block
IAQ COM
COM
IAQ 2-10
2-10 Vdc
IAQ 24V
24 Vac
ACT 2-10
2-10 Vdc
ACT COM COM
ACT 24V
24 Vac
Table 2. Economizer Module - Right hand terminal blocks.
Label
Type
Top Right Terminal Block
n/a
SD-O/B
24 Vac IN
OCC
24 Vac IN
E-GND
EGND
EXH1
24 Vac OUT Exhaust Fan 1 Output
AUX
24 Vac OUT Programmable:
Bottom Right Terminal Block
Y2-I
24 Vac IN
Y2-O
24 Vac OUT Y2 out - Cooling Stage 2 Output to
Y1-I
24 Vac IN
Y1-O
24 Vac OUT Y1 out - Cooling Stage 1 Output to
C
COM
R
24 Vac
5
JADE™ ECONOMIZER MODULE
Description
Mixed Air Temperature Sensor
(polarity insensitive connection)
Outside Air Temperature Sensor
(polarity insensitive connection)
(polarity insensitive connection)
Air Quality Sensor Common
Air Quality Sensor Input
(e.g. CO
sensor)
2
Air Quality Sensor 24 Vac Source
Damper Actuator Output (2-10 Vdc)
Damper Actuator Output Common
Damper Actuator 24 Vac Source
Description
The first terminal is not used
Shut Down (SD) Conventional only
or
Heat Pump Changeover (O/B)
Occupied / Unoccupied Input
Earth Ground
Exhaust fan 2 output
or
ERV
or
System Alarm output.
Y2 in - Cooling Stage 2 Input from
space thermostat
stage 2 mechanical cooling
Y1 in - Cooling Stage 1 Input from
space thermostat
stage 1 mechanical cooling
24 Vac Common
24 Vac Power (Hot)
63-2700—01