Honeywell JADE W7220 Product Data page 14

Economizer module
Table of Contents

Advertisement

JADE™ ECONOMIZER MODULE
Menu
Parameter
ADVANCED
MA LO SET
SETUP
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
INTERSTG DLY
SD INPUT
DCVCAL ENA
CHECKOUT DAMPER VMIN-HS
DAMPER VMAX-HS
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1-O
CONNECT Y2-O
CONNECT AUX
ALARMS(_) MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
DA ENTHL ERR
SYS ALARM
NOTE: The alarms listed are examples. Additional alarms display depending on the parameter settings and
configuration.
a
Table 5 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
b
When values are displayed, pressing and holding the
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
63-2700—01
Table 5. Menu Structure
Parameter
Parameter
Default
Value
Range and Increment
45ºF
35 to 55 ºF;
increment by 1º
CLO
CLO
MIN
0ppm
0 to 500 ppm;
increment by 10
2000ppm
1000 to 3000 ppm;
increment by 50
2.0h
0 to 4.0 hours or OFF;
increment by 0.5
5 min
1 to 9 minutes
increment by 1
CLO
CLO
OPN
MAN
MAN (manual)
AUTO
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
) sensor, then none of the DCV parameters appear.
2
or
14
a
. (Continued)
b
Temp to activate Freeze Protection (close damper and alarm if
temp falls below setup value)
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ppm level to match CO2 sensor start level.
CO2 ppm span to match CO2 sensor.
Delay after stage 2 for cool has been active. Turns on 2nd stage of
cooling when economizer is 1st stage and mechanical cooling is
2nd stage. Allows three stages of cooling, 1 economizer and 2
mechanical.
OFF = no Stage 3 cooling.
Delay between stages 1 and 2 for cool
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 Vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed for
CLO. All other controls, e.g., fans, etc. will shut off.
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA and MA sensor conditions. See
Product Data sheet 63-2700 for details. Requires all 3 RA, OA and
MA sensors.
Positions damper to VMIN position
Positions damper to VMAX position
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make
sure you pause in this mode to allow for exhaust contacts to
energize due to the delay in the system.
Positions damper to the fully closed position
Closes the Y1-O relay (Y1-O)
Closes the Y2-O relay (Y2-O)
Energizes the AUX output. If Aux setting is:
• NONE – no action taken
• ERV – 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for ERV
d
operation.
• SYS – 24 Vac out. Issues a system alarm.
Alarms display only when they are active. The menu title "ALARMS
(_)" includes the number of active alarms in parenthesis ().
When AUX is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX terminal has 24 Vac out.
button causes the display to automatically increment.