is an 8-character M-Bus ID used for secondary addressing on the
Falcon MJ. We recommend that the serial number of the connected
water meter is programmed here.
Default: Secondary address is set as the last 8 digits of the module´s
SN
Medium
describes the medium to be measured on the selected Falcon MJ.
Selection: water, hot water, cold water, hot/cold water
Current time
is the current date and time inside the module This field can only be
edited, and changed in the module if the check-box "Edit Time" is
activated. The "Read clock of PC" control button will make a onetime
transfer of the PC's current time into this window. A click on the
control arrow at the right of the date field will open a calendar for
convenient selection of the date.
Edit Time
activation of this control check-box permits editing and programming of the
current date and time. This checkbox will automatically deactivate again after
parameterization has been done successfully.
Volume
is the current meter index in liters. By checking the box "Change volume" the
meter index can be updated.
Only possible if write protection is OFF and the "change volume" box is
checked.
Volume (backward)
is the meter count in litres for the amount of backflow
Change volume
activation of this check-box permits editing the "Volume" and "Volume
(backwards)" fields. This check-box will automatically deactivate again after
parameterization was done successfully.
Instantaneous Flow rate
displays the current flow in [l/h].
Falcon MJ M-Bus Operating instructions
05/18 Generation 1.2
Page 8 of 38