V5097A-E
Industrial Gas Valves

APPLICATION

The V5097A-E Gas Valves are used with the V4055, V4062
and V9055 Fluid Power Actuators to control gas flow to
commercial and industrial burners.
While it is possible to combine any V5097 gas valve with any
V4055, V4062, or V9055 fluid actuator, a limited range of
combinations apply to the application most often used. See
Table 1.

FEATURES

• Used with natural or liquefied petroleum (LP) gases.
• V5097 normally closed valves are rated for final shutoff
service (safety shutoff).
• V5097A,C,D,E Valves are for on-off service.
• V5097B Valve has a characterized guide and in
combination with the V4055, V4062 and V9055 Fluid
Power Actuators, provides slow-opening, HI-LO-OFF,
and modulating functions, respectively.
• V5097C,E Valves have a double seal and are used
with V4055D,E Fluid Power Actuators to provide
proof-of-closure switch and valve seal overtravel
interlock.
• V5097D,E Valves are for high pressure applications
(see Table 2).
• Two valve body types (small and large) applicable to
seven pipe sizes:
- Small body type for 3/4 in. (19 mm), 1 in. (25 mm),
1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51
mm) pipes.
- Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm)
and 3 in. (76 mm) pipes.
• Eight pipe adapter sizes 3/4 in. (19 mm) to 3 in. (76 mm)
have NPT or BSP-PL threaded connections.
• V5097 version provides three 1/4 in. upstream and
two 1/4 in. downstream taps and plugs. CE version
provides an additional downstream tap and plug.
• Valve body rating of 75 psi (5 bar); body passes
Underwriters Laboratories Inc. burst test.
• Yellow SHUT indicator attached to the valve stem
provides indication of the valve closed position.
• Unpainted die-cast aluminum body.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Operation and Checkout ..................................................
Service Information .......................................................... 10
PRODUCT DATA
Contents
1
1
2
2
6
8
9
65-0230-07

Advertisement

loading

Summary of Contents for Honeywell V5097A-E

  • Page 1: Table Of Contents

    — Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm) The V5097A-E Gas Valves are used with the V4055, V4062 and 3 in. (76 mm) pipes. and V9055 Fluid Power Actuators to control gas flow to •...
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 V5097A-E INDUSTRIAL GAS VALVES Table 2. Industrial Gas Valve Models: Pipe Adapter Ratings: See Table 4. Model Number Features Gas Pressure Limit Switch Mounting: Two 1/4 in. NPT V5097A Low pressure on-off (with quick-opening or BSP-PL upstream and downstream tapping and plug.
  • Page 4 V5097A-E INDUSTRIAL GAS VALVES 5 (127) 6-3/4 (171) 1-9/32 (33) OCTAGON ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. VALVE DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J OCTAGON SIZE (IN.)
  • Page 5 V5097A-E INDUSTRIAL GAS VALVES 6-3/4 (171) 5 (127) 1-9/32 (33) OCTAGON ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. VALVE DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J OCTAGON SIZE (IN.)
  • Page 6: To Size Two Identical Valves Piped In Series

    5. Use the cfh capacity (for 0.64 or the corrected cfh from step 4) for determining the gas valve size in Fig. 4. Honeywell gas valve capacities are shown in cubic feet per 6. Determine the maximum pressure drop across the valve...
  • Page 7 V5097A-E INDUSTRIAL GAS VALVES 3. Find the pressure drop across the first valve by For example, a valve capacity of 2670 cfh based on 0.72 sp gr assuming it to be 45 percent of the total pressure drop. gas is required. What valve capacity, based on 0.64 sp gr gas, 4.
  • Page 8: Installation

    V5097A-E INDUSTRIAL GAS VALVES 6 7 8 9 1 6 7 8 9 1 6 7 8 9 1 100.0 100.0 (25) 10.0 (2.5) (0.25) 1000 10,000 100,000 (2.8) (28) (283) (2830) CAPACITY IN cfh (m h) FOR GAS WITH SPECIFIC GRAVITY OF 0.64 (1 cfh = 0.0283 m M11687D Fig.
  • Page 9: Operation And Checkout

    V5097A-E INDUSTRIAL GAS VALVES Checkout WARNING Explosion Hazard And Electrical Shock Hazard. WARNING Can cause explosion, serious injury or death. 1. Turn off gas supply before starting installation. Explosion Hazard And Electrical Shock Hazard. 2. Disconnect power supply for valve actuator before Can cause explosion, serious injury or death.
  • Page 10: Service Information

    V5097A-E INDUSTRIAL GAS VALVES SERVICE INFORMATION Table 6. V5097 Valve Allowable Leakage Rate. Minimum V5097 Maximum No. of WARNING Pipe Allowable No. of Seconds Adapter Leakage Bubbles in for 10 Explosion Hazard And Electrical Shock Hazard. Size (in.) Medium SCCH 10 sec.
  • Page 11 V5097A-E INDUSTRIAL GAS VALVES Seal Assembly Replacement (Fig. 6) around the valve stem. Avoid using a cleaning solu- tion as it may damage the rubber seals used in the When removing the bonnet to inspect and clean the valve, valve.
  • Page 12 V5097A-E INDUSTRIAL GAS VALVES Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2009 Honeywell International Inc. 65-0230—07...