Table 5-7 Reader Settings Description - Honeywell IP-AK2 Installation And Configuration Manual

Access control unit
Table of Contents

Advertisement

Define the time zone during which the reader will be disabled. When the reader is
disabled, neither exit nor entry by Card and PIN mode or Card or PIN mode is
allowed.
Define the time zone during which the reader will be in lockdown mode. When the
reader is in lockdown mode, entry is prevented but egress is still allowed.
Define the reader's access mode (the combination of card and/or PIN entry required
by the reader). Note that the access mode defined here for the door can be
overridden by a card assigned with a VIP card type (see
for assigning a VIP card type).
Configure the anti-passback feature. When enabled, the anti-passback feature
prevents an entrant to an area from passing his card back to another potential
entrant. Note that anti-passback must first be enabled on the Panel Attributes page.
Refer to the descriptions in the table below to configure reader:

Table 5-7 Reader Settings Description

Setting
Description
Reader Name
The unique name identifies the device.
Specifies the validation conditions required at the door before access is
granted. For each access mode, you must also select a time zone from the
drop-down list. The time zone is the schedule by which the access mode is
effective.
Disabled - Allows neither exit nor entry by Card and PIN mode or Card or PIN
mode. Free egress is not allowed
Access Mode
Lockdown - Denies door entry but allows egress.
Time Zones
Card and Pin - Grants access only with both a successful card read and a valid
PIN entry at the door's keypad. You can perform the card read and PIN entry in
either sequence.
Card or Pin - Grants access with either a successful card read or a valid PIN
number entry at the door's keypad.
PIN Only - Grants access with only a valid PIN number.
Card Only - Grants access with only a successful card read.
Configures the anti-passback feature, which prevents an entrant to an area
from passing his card back to another potential entrant. Note that anti-passback
must first be enabled at the Panel Attributes page.
Enabled - Enables the anti-passback feature.
Hard - Does not allow a second entry on the same card without an exit.
Anti-Passback
Soft - Allows a second entry on the same card without an exit; however, an
event is generated that indicates the second entry.
Out - Applies to readers located inside the area. Cardholders use these readers
when attempting to exit the area.
In - Applies to readers located outside the area. These are readers that
cardholders use when attempting to enter the area.
Click【Update】to submit changes.
Access mode is priority-preemption mechanism. The priority is decreasing from
Note
Disable mode to Card Only mode. Higher priority will be identified first.
Honeywell
Creating Card
on page
38
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents