Wiring; Settings And Adjustments - Honeywell C6097A Product Data

Pressure switches

Advertisement

WIRING

WARNING
Electrical Shock Hazard.
Can cause serious personal injury or death.
Disconnect power supply before beginning installation.
More than one disconnection can be involved.
Make sure that all wiring agrees with all applicable local
codes, ordinances and regulations. An opening is provided to
accommodate rigid conduit or armored cable for line voltage
operation (see Fig. 3 and 4). Do not overload the switch
contacts (see Switch Ratings in the Specifications section).
The switching schematic is shown in Fig. 5.
Fig. 3. C6097 (manual reset switch model)
with cover removed.
Fig. 4. C6097 (recycle model) with cover removed.

SETTINGS AND ADJUSTMENTS

Pressure Setpoint Adjustment
To adjust the pressure setting, turn the setpoint adjustment
dial (Fig. 3, 4 and 5) clockwise
pressure setting and counterclockwise
pressure setting.
NO
NC
C
C6097A BREAKS C-NO, MAKES C-NC ON PRESSURE
1
FALL. MANUAL RESET MODELS LOCK OUT.
2
C6097B BREAKS C-NC, MAKES C-NO ON
PRESSURE RISE AND LOCKS OUT.
Fig. 5. C6097 schematic.
5
C6097A,B PRESSURE SWITCHES
to increase the
to decrease the
2
1
M17123
65-0237—1