AMC2 Modular Controller
AMC2‑4W_UL
en
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Bosch AMC2 Series

  • Page 1 AMC2 Modular Controller AMC2‑4W_UL Installation Manual...
  • Page 3: Table Of Contents

    RS-485 for extension modules 4.10 Wiegand Interface for Card Readers 4.11 Connecting Relay Outputs 4.12 Connecting Analog Input Devices 4.13 Tamper Protection UL Requirements System Requirements 5.1.1 Computer 5.1.2 Monitor 5.1.3 Printer Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 4: En | Table Of Contents

    UL 294 Level Descriptions Installation Instructions Operating Status Display of the AMC2 Configuring the Ethernet Interface Troubleshooting 6.3.1 Resetting the Software 6.3.2 Resetting the Device to Factory Default Technical Data Appendices Connecting Diagrams Index 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 5: Safety Instructions

    If the unit has been exposed to water and/or inclement weather (rain, snow, etc.). – If the unit does not operate normally when following the operating instructions. Adjust only those controls specified in the operating instructions. Improper Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 6 12V DC. Voltage input must never exceed 15V DC. – For UL installations, the Bosch APS-PSU-60 power supply may be used, and must be located in the same room as the connected AMC2 device. Recommended maximum distance between power supply unit and AMC2 is 3 m (9.84 ft).
  • Page 7 AMC2 Modular Safety Instructions | en Controller – For UL installations, lightning protection used must be UL listed. 11. The units should be installed in locations with restricted access. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 8: Fcc & Ices Information

    Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio/TV technician for help 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 9: Safety Precautions

    Risk of explosion of Lithium battery The battery can explode if it is replaced incorrectly. Replace only with the same type as recommended by the manufacturer. Dispose used batteries according to the battery manufacturer’s instructions. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 10 0°C to 50°C. Disposal Your Bosch product is designed and manufactured with high- quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your household waste.
  • Page 11: Unpacking

    If any parts are missing, inform your customer service representative or a Bosch Security Systems salesperson. The shipping carton is the safest transport container for the unit. Store it and the other packaging material for future use. If the unit has to be sent back, use the original packaging.
  • Page 12: Important Information

    Bosch Security Systems retains all rights not expressly granted. Nothing in this license constitutes a waiver of Bosch’s rights under the U.S. Copyright laws or any other federal or state law. If you have any questions concerning this license, please, write...
  • Page 13: Internet

    Tips and shortcuts may also be included in such notes. Internet If you are interested in further information on this product or information on other products, please consult our website at http://www.boschsecurity.com. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 14: Introduction

    This guarantees autonomous access decisions and complete access registrations even if the management host system is offline. The built in compact flash card provides adequate storage capability for cardholders and events. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 15 If the eight inputs and eight outputs on board are not enough to configure the system, up to three additional extensions (AMC2-8IOE, or AMC2-16IOE) can be connected. The extensions offer 8 or 16 additional inputs and outputs. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 16: Equipment Configuration

    Lithium battery for buffering of static RAM and real time clock (RTC). The battery life is estimated at 10 years, nevertheless an error message is generated if the voltage sinks below a preset minimum level. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 17 UL installations. 10 Docking port for compact flash memory 11 Configurable RS-232 host interface (ribbon cable connector). This host interface is not used for UL installations. 12 Configurable 10/100 Mbit/s Ethernet interface. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 18 16 Wiegand interfaces forup to 4 card readers 17 Connectors for eight analog inputs 18 Connectors for eight relay outputs Notice! All connectors, with the exception of the Ethernet host interface, are pluggable screw clamp terminals. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 19 19 Jumper for setting either voltage free relay output (“dry” mode) or looped-in voltage from the AMC2 internal power supply (“wet” mode). 20 Jumper: Equalization of potential between different systems and earth ground (shield) Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 20: Performance Characteristics

    – Tamper contact for external covers Notice! For UL installations, the Bosch APS-PSU-60 power supply may be used, and must be located in the same room as the connected AMC2 device. Recommended maximum distance between power supply unit and AMC2 is 3 m (9.84 ft).
  • Page 21: System Overview

    System configurations for Access Control applications The minimum configuration consists of: – one PC with access control software – one AMC2-4W controller – one Bosch APS-PSU-60 power supply – one AMC2-UL01 enclosure The maximum configuration consists of: Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 22 AMC2-8IOE or AMC2-16IOE input/output modules – each controller can be extended with one AMC2-4WE extension module – the necessary number of Bosch APS-PSU-60 power supply – the necessary number of AMC2-UL01 or AMC2-UL02 enclosures Using Wiegand reader interfaces, up to four peripheral devices can be connected to each AMC2-4W.
  • Page 23: Installing

    [1], then push down the device and snap it onto the rail by pushing it towards the back [2]. Figure 4.1: Mounting the AMC2 on a mounting rail Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 24: Unmounting

    Push down the AMC2-4W until the lower edge snaps out of the mounting rail [1]. Pull the lower end of the AMC2-4W from the mounting rail [2]. Figure 4.2: Unmounting the AMC2 from a mounting rail 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 25: Opening The Case

    The AMC2-4W case consists of a top cover mounted with a two- point snap-in closure on a chassis. To open the case, push down the two snap-ins with a screwdriver, then swing the cover down. Figure 4.3: Opening the AMC2 case Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 26: Closing The Case

    Insert the hooks on the lower edge of the front cover into the lugs on lower edge of the plastic back cover [1]. Please ensure that the BOSCH logo is not upside-down. The upper edge of the front cover now aligns with the two-point snap-in closures on the upper edge of the back cover [2], and may thus be clicked gently into place.
  • Page 27: Cabling

    20,948 = 20,948 x 0.1 km x 1A = 2.1V Drop = 6.385 x 328 ft x 1A = 2.1V Drop Critical condition! Install the power supply closer to the controller. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 28 AMC2 is 3 m (9.84 ft). Notice! These specifications apply to power supply, readers, relay outputs, and extension interface. Regarding inputs, specific voltage-drop values need to be taken into account. Refer to Connecting Analog Input Devices, page 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 29: Grounding And Shielding

    The free end should be insulated to avoid inadvertent connections. If one device is fed power by another, the cable shielding should be applied to both sides. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 30: Grounding For Extension Interface

    Jumper B connects the internal ground of the AMC2-4W to the RS-485 ground of the slave interface. Only set jumper B (B2) if the AMC2-4W powers all other peripheral devices directly connected to it. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 31: Connecting Power Supply

    5 and 7 for power good Battery – pin 6 and 7 for power good DC Otherwise these pins must be short-circuited. Notice! To build a UL listed configuration, refer to UL Requirements, page 45 Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 32: Ethernet Host Interface

    AMC2 device is recognized by the remote server. You can accelerate this process by running the following command: ipconfig /flushdns This makes the AMC2 device immediately available by its name. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 33 AMC2 Modular Installing | en Controller Notice! Using the Ethernet connection, the switches 1 and 5 must remain in Pos. ON (=factory setting). Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 34: Rs-485 For Extension Modules

    You can find further information about the extension boards in their installation manuals. A complete connection diagram of the RS-485 extension module bus is shown in Connecting Diagrams, page 63. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 35 AMC2 Modular Installing | en Controller Figure 4.9: Connection of an extension module to an AMC2 Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 36: Wiegand Interface For Card Readers

    Refer to Connecting Diagrams, page 63 for a complete wiring diagram of the Wiegand reader interface . Notice! Reference UL Requirements, page 45 for readers approved for UL installations. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 37: Connecting Relay Outputs

    Figure 4.11: Location of the relay output connectors Each relay output can operate in ‘wet’ mode, using the AMC2-4W 's internal 12/24 Vdc power supply for external devices or ‘dry’ mode with potential free contacts for externally powered systems. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 38 If using locally manufactured products, please ensure that the specifications of the product are identical with the those listed above. A complete connection diagram of the relay output connectors is shown in Connecting Diagrams, page 63. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 39 Notice! Risk of damage to equipment Do not connect externally powered devices in wet mode. This can damage the AMC2-4W . Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 40 (D1) or wet ( D2) mode. Figure 4.14: Location of relay output jumpers (bottom side) Notice! The positions of the jumpers 1 and 2 are interchanged related to the corresponding interfaces. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 41: Connecting Analog Input Devices

    37. Figure 4.15: Location of the analog input connectors The AMC2-4W can also detect the wiring conditions ‘short circuit’ and ‘broken’, and hence trigger an alarm if the appropriate devices are connected. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 42 To detect the four states, the voltage drop in the connecting cable may not exceed special values. The following table shows the maximum values of permissible cable resistance depending on the used resistor combination. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 43 1900 Table 4.1: Maximum values of cable resistance per used resistor combination in Ohm Notice! For UL Access controls installations, only the R = 2k2 and R 2k2 End-of-Line resistors may be used. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 44: Tamper Protection

    This interface is a potential-free 2-pin pluggable screw connector marked with T. When not in use this tamper contact should be shorted. Figure 4.16: Location of the tamper protection contact 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 45: Ul Requirements

    For UL compliance, use only UL Listed 26-bit Wiegand format readers. The following Bosch model card readers were evaluated by UL for compatibility with the Bosch's APE 3.4 and 3.5 or BIS/ACE 4.5 Software System: – LECTUS secure 1000 WI –...
  • Page 46: System Requirements

    – USB Keyboard and Mouse Other Software – To run the AmcIpConfig application supplied (and the Bosch Video SDK), you need the .NET Framework 4.0 platform. – To create and display lists and reports, you must install Crystal Reports applications.
  • Page 47: Monitor

    – ACCESS CONTROL STANDBY POWER LEVEL II – An access control product for units employing Model APS-PSU-60 Power Supply for 12 VDC and 24 VDC Mode. Level II operates for 30 minutes. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 48: Installation Instructions

    It may not be used for connection to readers or other accessories. – All units are to be powered by the Bosch APS-PSU-60 power supply for UL installations. The power supply must be located in the same room as the connected AMC2 device.
  • Page 49 HVAC system may be supplied by an engine driven generator alone. A standby battery is not required to be used. For UL compliance, use only UL Listed 26-bit Wiegand format readers. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 50 AMC2 Modular en | UL Requirements Controller Black Battery Connection Earth Cable White R-485 Extension Connection 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 51 - Avoid any crossing of the conductors of the two categories. - Guide the conductors of the two categories through different knock-outs of the housing. For detailed diagram, refer to the drawing contained in the folder titled “_UL” on the delivered CD. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 52: Operating

    45 Status Display of the AMC2 The liquid crystal display delivers status information about the AMC2-4W . Push the 'Dialog' button to switch between different modes. Figure 6.1: Location of the ’Dialog’ button 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 53 N AMC-1234-5678 Network name of the AMC2 I 192.168.10.18 IP-address of the AMC2 G 192.168.10.255 IP-address of the gateway (Version V 00.44 or higher) M 255.255.255.0 Subnetmask (Version V 00.44 or higher) Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 54 Host activity: + = online - = offline "C" = Counter of the received data packages from the host interface. RS 485 Bus connection: A = Address 1 … H = Address 8 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 55: Configuring The Ethernet Interface

    Do not use special characters or spaces. The network name must start with a letter. The names are not case sensitive. Notice! Consult the AmcIpConfig tool’s own online help for details on configuring the AMC2-4W . Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 56: Troubleshooting

    As soon as it is online again, the AMC2-4W bootloader will download a fresh copy of the application program and configuration. If the problem persists please request technical support. 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 57 AMC2 Modular Operating | en Controller Figure 6.2: Resetting the AMC2 Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 58: Resetting The Device To Factory Default

    IP = [assigned by DHCP server or “0.0.0.0” if not available] – Subnet mask = [assigned by DHCP server or “0.0.0.0” if not available] – Password = no password Figure 6.3: Resetting the AMC2 to delivery state 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 59: Technical Data

    Tamper contact for external enclosures – RS-485 output power rated maximum 2.5 A @ 9.0-30 Vdc (voltage output is dependant on board voltage input) Power input 10 to 30 Vdc, max 3 A Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 60 (W/H/D) 232 x 90 x 63mm (8.9 x 3.5 x 2.5 in) Weight approx. 0.53kg (1.2lb) Notice! The voltage drop from the power supply to the AMC2-4W affects the AMC interfaces. The total drop must not exceed 2V! 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 61 To determine the environmental impact of an installation, take into account the most extreme values of all participating devices. To determine the vulnerability of an installation, take into account the most restrictive values of all participating devices. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 62 AMC2 Modular en | Technical Data Controller 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 63: Appendices

    To build a UL listed configuration, refer to UL Requirements, page 45 Connecting Diagrams Figure 8.1: Connectors on upper PCB TXD+ TXD- RXD+ not connected not connected RXD- not connected not connected Tab. 8.2: Ethernet Network socket (RJ45) Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 64 AMC2 Modular en | Appendices Controller Figure 8.2: Connector blocks of the AMC2-4W 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 65 Data 1 drain Shield orange green LED brown red LED yellow Beeper blue Hold violet Card Present Tab. 8.4: Wiegand interface AMC Notice! For reader settings refer to the respective reader manual. Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 66 Power supply for external devices (10V - 30V) Power supply for external devices (0V) Shield Data RxTx+ Data RxTx- Ground (PAG) Tab. 8.7: Host / Extension interface Tamper Contact, in Tamper Contact, out Tab. 8.8: External tamper contact 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 67: Index

    I/O board  34 transfer rates  59 inputs  18, 20, 41 interfaces Ethernet unmounting  55  24 extension  30, 59 host  17, 20, 32, 59 reader  36, 59 interfades extension  34  52 mounting  23 Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 68 AMC2 Modular en | Index Controller 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 69 AMC2 Modular Index | en Controller Bosch Access Systems GmbH 2018-09 | AMC2-4W_UL |...
  • Page 70 AMC2 Modular en | Index Controller 2018-09 | AMC2-4W_UL | Bosch Access Systems GmbH...
  • Page 72 Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com © Bosch Sicherheitssysteme GmbH, 2018...