Symptom: Wrong Date/Time - Honeywell LeaderLine DPR 100 C Product Manual

Table of Contents

Advertisement

10.2.9
SYMPTOM : Wrong date/time
POSSIBLE CAUSE
Date and time are lost
10.2.10 SYMPTOM : The alarm relay is inoperative or does not have the desired effect
POSSIBLE CAUSE
Configuration is incorrect.
The connectors are incorrectly fitted.
Alarm relay board
10.2.11 SYMPTOM : Analog input records outside specified accuracy tolerance
POSSIBLE CAUSE
Recorder configured for wrong sensor or
actuation.
"Range" not correct.
Recorder not configured for the correct
supply frequency.
The analog card is not correctly fitted.
Open circuit
Bad contact or bad setting on the switches
of input board
Environmental
limits.
Analog input card
conditions
outside
10. TROUBLESHOOTING
CORRECTIVE ACTION
Replace battery and contact your local office.
Refer to CK 152.
CORRECTIVE ACTION
Check the jumper selection on relay board
Check the "relay" parameter in the alarm
matrix.
Connect and refit. (Refer to pages 2-5 to 2-7)
Replace the board (Refer to CK 110)
CORRECTIVE ACTION
Check "sensor" and "actuation" configuration.
Check "range" configuration.
Check "frequency" (50/60 Hz) configuration.
Reconnect it.
Check sensor, leads and input terminals.
Check the switch position. Push the switches
completely on the high or low position.
rated
Ensure that ambient temperature and relative
humidity are within limits given in the product
specification sheet.
Replace analog input card. (Refer to CK 110)
10-11