Input Calibration
RTD Inputs
Refer to Figure 6-4 and wire the indicator according to the procedure given in Table 6-5.
Make sure the jumper at S101 is in the #2 position (Figure 2-2).
Step
1
Connect the copper leads from the calibrator to the Input terminals as shown in Figure
6-4.
Place current source at zero before switching on.
2
Do not switch current sources ON/OFF while connected to the UDC2300 input.
3

Figure 6-4 Wiring Connections for RTD (Resistance Thermometer Device)

Radiamatic, Millivolts, Milliamperes, or Volts
Refer to Figure 6-5 and wire the indicator according to the procedure given in Table 6-6.
Make sure the jumper at S101 is in the #2 position for, mV, Volts, or the #4 position for
mA (Figure 2-2).
Table 6-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts,
Step
Connect the copper leads from the calibrator to the Input terminals as shown
1
in Figure 6-5.
2
Place current source at zero before switching on.
3
Do not switch current sources ON/OFF while connected to the UDC2300 input.
For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.5 – Configuration Set Up prompt
INPUT1, function prompt EMISS.
44

Table 6-5 Set Up Wiring Procedure for RTD Inputs

Decade
Resistance
Box
or Volts Inputs (Except 0-10 Volts)
UDC2300 Indicator Product Manual
Action
8
+
_
7
6
R
24875
Copper Leads
Equal Length
Action
10/00

Advertisement