Honeywell CD3000M-2PH User Manual page 43

Thyristor unit, from 125a to 700a
Table of Contents

Advertisement

Honeywell
9.3.8 Command Table
Bit
Meaning
0
HB Calibration
1
Firing command
2
On-Off
3
RESET HB
N.B.: When unit is switch off all command parameter are set to 0
9.3.8.1 HB Calibration
Operations: Read / Write
Meaning:
It's a bit that starts the HB calibration procedure
When this bit is zero start the calibration procedure and reset itself automatically at the end.
9.3.8.2 Firing command
Operations: Read / Write
Meaning:
It's a command bit used to switch from analog external command to command via RS485
0
= Command of analog input
1
= Command of RS485 input
9.3.8.3 On-Off
Operations: Read / Write
Meaning:
Its' an enable bit to switch ON-OFF the power.
0
= Power disabled
1
= Power enabled
9.3.8.4 HB RESET
Operations: Read / Write
Meaning:
It's a command bit to reset HB alarm.
This parameter has to be at 0 to have the alarm working properly
0
= Reset disabled
1
= Reset enabled
www.honeywell.com/imc
CD3000M-2PH from 125A to 700A
Notes
Read /write
( normal mode set to 0)
Read /write
Read /write
Read /write
( normal mode set to 0)
40
0=Off -
1=ACTVATE Calibration
0=from terminal - 1=from RS485
0=Off -
0=Off -
User's Manual
1=On
1=RESET
Bit 0
Bit 1
Bit 2
Bit 3