8. Fuses and fuseholder

8.1 Fuses and Fuse Code
CD3000M unit must be protected by fuses against short circuit selecting the proper I²t that must
be lower than thyristor one. The same caution must be taken if Circuit Breaker is used. Remember
that is very difficult to protect the thyristor if this choice is done.
WARNING!! Equipment short circuit protected by Semiconductor Fuse type
with proper I
Bussmann Div - Cooper (UK) Ltd
(200 kA
RMS
Sizes
Fuse Mod. No.
/modéle fusible
125A
200 FEE
400A
550 FMM
450A
2x 315 FM
500A
2x 315 FM
600A
2x 450 FMM
700A
2x 450 FMM
SIBA (300kA @ 600V, 200kA @700V)
150A
20 559 20
200A
20 559 20
275A
20 559 20
High speed fuses are only used for the thyristor protection and can not be used to
protect the installation.
The user installation must be protect by electromagnetic circuit breaker or by fuse
isolator.
The warranty of thyristor is null if no proper fuses are used. See tab above.
www.honeywell.com/imc
CD3000M-2PH from 125A to 700A
2
t
Symmetrical A.I.C.)
Current
(A
)
(A
RMS
200
11400
550
215000
315
77000
315
77000
450
105000
450
105000
250
44000
315
77000
315
77000
Ferraz Shawmut SA
(200 kA
2
I
t
V ac Fuse Mod. No.
2
sec)
/modéle fusible
6,6 URY 000
660
BS88 200
6,6 URZ 2X000
660
BS88 Z 550
2 x 6,6 URB 000
660
BS88 315
2 x 6,6 URB 000
660
BS88 315
2x 6,6 URZ
660
2X000 BS88 450
2x 6,6 URZ
660
2X000 BS88 450
FERRAZ (200kA @ 660V)
6,6 URB 000
660
BS88/250
6,6 URB 000
660
BS88/315
6,6 URB 000
660
BS88/315
30
Symmetrical A.I.C.)
RMS
Current
(A
)
RMS
200
550
315
315
450
450
250
315
315
User's Manual
2
I
t
Vac
2
(A
sec)
16000
660
208000 660
82000
660
82000
660
126000 660
126000 660
52000
660
82000
660
82000
660