Auxiliary Supply - Honeywell CD3000M-2PH User Manual

Thyristor unit, from 125a to 700a
Table of Contents

Advertisement

Honeywell

6.1 Auxiliary supply

Warning: this procedure can be done just by specialized personnel.
To change auxiliary supply voltage sold the correct link-jumper on main PCB
Auxiliary supply jumpers for S9 and S10 sizes
Auxiliary supply jumpers for S14 size
230V Auxiliary supply
To set the auxiliary power
supply to 230V, close J9 and
J11 and open J10 as shown
below.
J11
J10
J9
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage
(to the load ), use an external transformer.
If load voltage is not included in range of 230V ±15% or 460V +15% provide an external
transformer with primary equal to load voltage and secondary 230V if your unit is setted to
230V.
www.honeywell.com/imc
CD3000M-2PH from 125A to 700A
J11
J10
J9
J11
J10
J9
460V Auxiliary supply
To set the auxiliary power
supply to 460V, close J10
and open J9 and J11 as
shown below.
J11
J10
J9
20
600V Auxiliary supply
This is a special version on request.
In this case the unit is supplied
already configured.
J11
J10
J9
User's Manual